Skip to main content
Schneider Electric GV2LC0216 — Molded Case Circuit Breakers (MCCB)

Schneider TeSys GV2LC0216 Enclosed DOL Starter, 14 A, 3P

MPNGV2LC0216
Active

Schneider Electric TeSys GV2-LC enclosed DOL starter, GV2LC0216, 3-pole, 14 A thermal protection adjustment range, IP54 polycarbonate enclosure.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2LC0216 — Identification
ParameterValue
Product / component typeEnclosed DOL starter
GV2LC0216 — Mechanical
ParameterValue
Height166 mm
Width88 mm
Depth173 mm
GV2LC0216 — Electrical
ParameterValue
Breaking capacity10 kA Icu at 500 V conforming to IEC 60947-2 100 kA Icu at 220...230 V conforming to IEC 60947-2 20 kA Icu at 440 V conforming to IEC 60947-2 50 kA Icu at 400...415 V conforming to IEC 60947-2
[Ue] rated operational voltage690 V
GV2LC0216 — Specifications
ParameterValue
Poles description3P
Trip unit technologyMagnetic
Device short nameGV2LC
StandardsVDE 0660-102 EN 60947 IEC 60439-1 IEC 60947-4

Product details

The Schneider Electric TeSys GV2LC0216 is an enclosed direct-on-line (DOL) motor starter built around a magnetic-trip circuit breaker. It's a self-contained unit — the breaker, thermal overload, and enclosure come as one assembly, so there's no separate contactor-and-relay stack to wire up. The thermal protection adjustment range tops out at 14 A, and the magnetic trip fires at 13 x In (±20 %), which means it handles inrush without nuisance trips on standard induction motors. Rated operational voltage goes to 690 V, and the breaking capacity (Icu per IEC 60947-2) runs from 10 kA at 500 V up to 100 kA at 220–230 V — so it's sized for industrial panels where fault current can vary by supply voltage. The IP54 polycarbonate enclosure keeps dust and splash out, making it a fit for machine-side mounting rather than a clean control cabinet. Standards compliance covers VDE 0660-102, EN 60947, IEC 60439-1, and IEC 60947-4 — the usual suite for motor starters and distribution in European and IEC-based installations.

The 14 A thermal adjustment range sets the motor FLA it can protect — you set the dial to match the motor nameplate. The magnetic trip at 13 x In (±20 %) means it holds through starting current (typically 6–8 x FLA) and only clears on a hard short. That's standard for a DOL starter on a general-purpose induction motor. Breaking capacity spans 10 kA at 500 V to 100 kA at 220–230 V. The number that matters for your panel is the SCCR at your supply voltage — if your available fault current is 18 kA at 400 V, the 20 kA rating at 440 V covers it. The 100 kA figure at 230 V is typical for low-voltage industrial networks. IP54 means the enclosure is dust-protected and splash-resistant — fine for machine-side or washdown-adjacent areas, but not for hose-down or submersion. The polycarbonate shell holds up in industrial atmospheres where a metal enclosure might corrode. Cable entries are 2 x 20 mm and 2 x 25 mm ISO knockouts at top and bottom — enough for standard motor and supply cables through PG-type glands. The rotary handle is black, and the enclosure accepts 1–3 padlocks (Ø 8 mm) in the OFF position for lockout/tagout.

Physical dimensions and mounting

The enclosure measures 166 mm high, 88 mm wide, and 173 mm deep. That depth includes the rotary handle and cable entries — account for it when spacing on a machine frame or sub-panel.

Frequently asked questions

What is the closest alternative to the GV2LC0216 in the TeSys family?

Within the TeSys GV2-LC enclosed starter range, the GV2LC0216 is a specific thermal setting (14 A). The closest sibling would be a GV2LC unit with a different thermal adjustment range — for example, a 10 A or 20 A variant. The mechanical footprint and enclosure are identical across the range; only the trip unit changes. No pin-compatible drop-in exists outside the GV2LC family because the enclosure and breaker are integrated.

What is the depth of the GV2LC0216?

The depth is 173 mm, measured from the back of the enclosure to the front of the rotary handle.

What is the width of the GV2LC0216?

The width is 88 mm.

What compliance documentation does Schneider provide for the GV2LC0216?

The GV2LC0216 is certified to VDE 0660-102, EN 60947, IEC 60439-1, and IEC 60947-4. These cover the product safety and performance standards for motor starters and distribution in IEC markets. Schneider typically provides a declaration of conformity and the relevant test reports upon request through their documentation portal.

MPN
GV2LC0216