Skip to main content
Schneider Electric GV2LC0220R — Miniature Circuit Breakers (MCB)

TeSys GV2LC0220R Enclosed DOL Starter, 18 A, IP54

MPNGV2LC0220R
Active

Schneider Electric TeSys GV2-LC enclosed DOL starter, GV2LC0220R, 18 A thermal protection, 3-pole, magnetic trip, IP54 polycarbonate enclosure, rotary red handle.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2LC0220R — Identification
ParameterValue
Product range (series)TeSys
Product/component typeEnclosed DOL starter
GV2LC0220R — Ratings
ParameterValue
Poles configuration3P
Breaking capacity10 kA Icu at 500 V conforming to IEC 60947-2 100 kA Icu at 220...230 V conforming to IEC 60947-2 20 kA Icu at 440 V conforming to IEC 60947-2 50 kA Icu at 400...415 V conforming to IEC 60947-2
Rated operational voltage (Ue)690 V
GV2LC0220R — Protection
ParameterValue
Trip unit technologyMagnetic
GV2LC0220R — Mechanical
ParameterValue
Control typeRotary handle red
Width88 mm
Height166 mm
Depth173 mm
GV2LC0220R — Environmental
ParameterValue
IP degree of protectionIP54 conforming to IEC 60529
GV2LC0220R — Approvals
ParameterValue
StandardsIEC 60439-1 IEC 60947-4 EN 60947 VDE 0660-102

Product details

The Schneider Electric TeSys GV2LC0220R is an enclosed direct-on-line (DOL) starter — a combined circuit breaker and motor starter in one IP54 polycarbonate box, ready to mount near the motor rather than inside a central panel. It is a non-reversing, 3-pole unit with a magnetic trip unit and a thermal protection adjustment range set at 18 A. The polycarbonate housing resists corrosion in washdown or outdoor areas, and the rotary red handle gives a local on/off that can be locked off with up to three 8 mm padlocks.

The interrupting ratings are given per IEC 60947-2 across several voltage levels. At 400...415 V the unit clears 50 kA Icu, and at 440 V it clears 20 kA Icu. At 500 V it clears 10 kA Icu, and at 220...230 V it clears 100 kA Icu.

Cable entry and enclosure details

The box accepts cable entries at top and bottom: two 20 mm ISO knockouts and two 25 mm ISO knockouts per end. That gives flexibility for running conduit or cable glands without drilling. The overall dimensions are 173 mm deep, 88 mm wide, and 166 mm high, so it fits a compact footprint on a machine frame or wall bracket.

Frequently asked questions

What are the key ratings I need to check for fit?

The thermal protection is fixed at 18 A. The breaking capacity varies with voltage: 100 kA at 220...230 V, 50 kA at 400...415 V, 20 kA at 440 V, and 10 kA at 500 V, all per IEC 60947-2. The enclosure is IP54, and the cable entries are 20 mm and 25 mm ISO knockouts at top and bottom.

What compliance standards does this starter meet?

It complies with IEC 60439-1, IEC 60947-4, EN 60947, and VDE 0660-102. These cover the low-voltage switchgear and motor-starter requirements for European and international installations.

MPN