The GV2LE04 is a 3-pole motor circuit breaker from the TeSys GV2 range, rated at 0.63 A continuous. It uses magnetic-only trip technology with a fixed magnetic tripping current of 9.3 A — designed for motor protection where short-circuit clearance is needed without the thermal overload curve. Breaking capacity is 100 kA Icu across 230–690 V AC 50/60 Hz, giving it headroom for high-fault panels.
Certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40:Annex JJ. Fire resistance rated at 960 °C per IEC 60695-2-11. IP20 housing.
Panel integration — mounting and wiring
Mounts in horizontal or vertical orientation. Screw clamp terminals accept 1–6 mm² solid or 1.5–6 mm² flexible without cable end, or 1–4 mm² flexible with cable end. Tighten to 1.7 N·m. Depth: 3.09 in (78.5 mm); width: 1.8 in (45 mm); height: 3.5 in (89 mm). Climate withstand per IACS.