The Schneider Electric TeSys GV2P02KD09B7 is a direct on-line motor starter with a 0.25 A line rated current, sized for a 0.06 kW motor at 400/415 V AC. It combines a contactor and thermal-magnetic overload in a single 45 mm wide package, controlled via a rotary knob. The 24 V AC coil is standard, and the unit clips onto a 35 mm symmetrical DIN rail or panels with two M4 screws. Rated for continuous duty per IEC 60947-4-1, it carries a 100 kA breaking capacity at 400/415 V AC under IEC 60947-2 — meaning it can safely interrupt a fault current up to that level without upstream damage. The magnetic tripping current is set at 2.4 A, and the unit is rated for 100,000 electrical cycles in AC-3 duty at 440 V.
The 45 mm width and 89 mm height fit standard enclosure layouts. Pollution degree 3 rating confirms it handles conductive pollution typical of industrial environments.