Schneider Electric GV2P03KD09B7 — Miniature Circuit Breakers (MCB)

TeSys GV2P03KD09B7 Motor Starter, 0.4A, 0.09kW at 400V

MPNGV2P03KD09B7
Obsolete

Schneider Electric TeSys GV2P03KD09B7 motor starter, direct on-line contactor, 0.4 A rated current, 0.09 kW at 400/415 V AC, 100 kA breaking capacity, IP20, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2P03KD09B7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2P03KD09B7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Rated operational voltage (Ue)Power circuit Power circuit 10 MOhm for signalling circuit
Rated insulation voltage (Ui)690 V AC 50/60 Hz IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV IEC 60947-2
Network frequency50/60 Hz IEC 60947-4-1
Utilisation categoryAC-4 AC-1 AC-3
GV2P03KD09B7 — Protection
ParameterValue
Electrical durability (cycles)100000 cycles AC-3 440 V
Mechanical durability (cycles)100000 cycles
GV2P03KD09B7 — Mechanical
ParameterValue
Control typeRotary knob
Terminal connection typescrew clamp terminals 2 0.002...0.009 in² (1...6 mm²) solid screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) flexible without cable end screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) flexible with cable end
Terminal tightening torque15.05 lbf.in (1.7 N.m) screw clamp terminals
Width1.8 in (45 mm)
Height3.5 in (89 mm)
Depth3.8 in (97 mm)
GV2P03KD09B7 — Environmental
ParameterValue
Operating ambient temperature23...140 °F (-5...60 °C)
Storage ambient temperature-76...176 °F (-60...80 °C)
IP degree of protectionIP20 IEC 60529
Pollution degree3
GV2P03KD09B7 — Approvals
ParameterValue
StandardsNF C 63-120 IEC 60947-4-1 NF C 79-130 IEC 60947-2 NF C 63-650 CSA C22.2 VDE 0113 VDE 0660 EN 60204 IEC 60947-1 UL 508
GV2P03KD09B7 — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2

Product details

The Schneider Electric TeSys GV2P03KD09B7 is a direct on-line motor starter rated at 0.4 A line current, sized for a 0.09 kW motor at 400/415 V AC 50/60 Hz three-phase supply. It's a 3-pole unit with a rotary knob control, built for continuous duty per IEC 60947-4-1. It covers utilisation categories AC-1 (resistive), AC-3 (squirrel-cage motor starting/running), and AC-4 (plugging/inching), so it handles both standard motor starts and more demanding reversing or jogging duty cycles.

Mounts on 35 mm symmetrical DIN rail or panel-screwed with 2 x M4 screws — the DIN clip is the faster option for production builds. Dimensions are 3.5 in (89 mm) high, 1.8 in (45 mm) wide, 3.8 in (97 mm) deep, so it occupies a single module width on the rail. IP20 finger-safe protection (IEC 60529) means it's intended for enclosed panels, not open washdown areas. Screw clamp terminals accept 1 to 6 mm² solid or 1.5 to 6 mm² flexible without ferrules; with ferrules, 1 to 4 mm². Tighten to 1.7 N·m (15.05 lbf·in).

Approvals include IEC 60947-4-1, IEC 60947-2, UL 508, CSA C22.2, and VDE 0660, so it passes inspection for panels destined for North American or European sites. Flame retardance is V1 per UL 94; glow-wire tested at 850 °C (1562 °F) per IEC 60695-2-1.

Frequently asked questions

What is the closest alternative in the TeSys family?

Within the TeSys GV2 series, the closest functional sibling would be a unit with the same frame size and breaking capacity but a different current rating matched to a larger or smaller motor. The deciding factor is the 0.4 A line current and 0.09 kW motor power at 400 V — step up to a higher-rated GV2 variant if the load exceeds that.

What compliance documentation is available for this part?

The starter carries IEC 60947-4-1, IEC 60947-2, UL 508, CSA C22.2, and VDE 0660 approvals. Flame retardance is V1 per UL 94, and it passes glow-wire at 850 °C per IEC 60695-2-1.