Product Overview and Key Ratings
The GV2P04KD09B7: The breaking capacity is rated at 100 kA Icu across the full voltage range from 230/240 V up to 690 V AC per IEC 60947-2, which means this starter can safely interrupt fault currents up to 100 kA without upstream cascading — a critical parameter for coordination studies in high-fault-capacity installations. Motor power ratings span 0.12 kW at 400/415 V AC up to 0.37 kW at 690 V AC, with a motor power range covering 1.1...2 kW at 200...240 V three-phase and 2.2...3 kW at 380...440 V three-phase. The utilization categories include AC-3 for motor control and AC-1 for resistive loads, with an electrical durability of 100,000 cycles at AC-3 440 V.
Dimensions are 3.5 in (89 mm) height, 1.8 in (45 mm) width, and 3.8 in (97 mm) depth, fitting standard enclosure layouts. Screw clamp terminals accept solid conductors from 1 to 6 mm², or flexible with cable end from 1 to 4 mm², with a tightening torque of 15.05 lbf.in (1.7 N.m). The operating position is any position, and the unit is rated for continuous duty per IEC 60947-4-1.