Schneider Electric GV2P05AE11TQ — Miniature Circuit Breakers (MCB)

Schneider GV2P05AE11TQ TeSys GV2 Motor Circuit Breaker, 1 A

MPNGV2P05AE11TQ
Obsolete

Schneider Electric TeSys GV2 motor circuit breaker, GV2P05AE11TQ, 1 A rated current, 100 kA breaking capacity, thermal-magnetic, 3-pole, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2P05AE11TQ — Identification
ParameterValue
Product nameTeSys GV2
Product rangeTeSys Deca
Product/component typeMotor circuit breaker
Device applicationMotor protection
GV2P05AE11TQ — Ratings
ParameterValue
Rated current (In)1 A
Poles configuration3P
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz conforming to IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1
GV2P05AE11TQ — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-1
Electrical durability (cycles)100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In
Mechanical durability (cycles)100000 cycles
GV2P05AE11TQ — Mechanical
ParameterValue
Control typeRotary handle
Terminal connection typePower circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end
Terminal tightening torque1.7 N.m - on screw clamp terminal
Width45 mm
Height89 mm
Depth97 mm
GV2P05AE11TQ — Environmental
ParameterValue
Operating ambient temperature-20...60 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
GV2P05AE11TQ — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2
GV2P05AE11TQ — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Product details

The Schneider Electric GV2P05AE11TQ is a TeSys GV2 motor circuit breaker rated at 1 A, designed for protecting 0.25 kW motors at 400/415 V AC and 0.55 kW at 690 V AC. This is a 3-pole device in the TeSys Deca range, suited for motor branch circuits in control panels. It carries AC-3 and AC-3e utilisation categories per IEC 60947-4-1, which is the standard for switching squirrel-cage motors during starting and plugging. The electrical durability is rated at 100,000 cycles under AC-3 at 415 V, matching the mechanical durability figure.

The 45 mm width and 89 mm height fit standard motor-starter footprints. The rotary handle provides local on/off control and a clear visual position indicator. Screw-clamp terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule, tightened to 1.7 N·m.

Compliance documentation is comprehensive: certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. It also meets IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for fire resistance (960 °C glow-wire test). The climatic withstand conforms to IACS for marine environments.

Frequently asked questions

What are the key ratings for this motor circuit breaker?

Rated current is 1 A with a magnetic trip threshold of 15.1 A. Breaking capacity is 100 kA Icu at 400/415 V AC. It protects motors up to 0.25 kW at 400 V and 0.55 kW at 690 V. The utilisation category is AC-3 / AC-3e per IEC 60947-4-1.

What standards does the GV2P05AE11TQ comply with?

It is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. It also meets IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for fire resistance, plus IACS for climatic withstand.

How is the GV2P05AE11TQ mounted and wired?

It snaps onto 35 mm DIN rail or mounts directly with two M4 screws. The screw-clamp terminals accept up to 6 mm² solid or 4 mm² flexible wire, tightened to 1.7 N·m. The built-in auxiliary contact block provides 1 NO + 1 NC contacts on the front.

MPN
GV2P05AE11TQ