Skip to main content
Schneider Electric GV2P06KD09B7 — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2P06KD09B7 Motor Starter, 1.6 A, 100 kA Ic

MPNGV2P06KD09B7
Obsolete

Schneider Electric TeSys GV2P06KD09B7 motor starter, 1.6 A line rated current, 100 kA Icu at 400 V, 3-pole, IP20, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2P06KD09B7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2P06KD09B7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Rated operational voltage (Ue)Power circuit Power circuit 10 MOhm for signalling circuit
Rated insulation voltage (Ui)690 V AC 50/60 Hz IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV IEC 60947-2
Network frequency50/60 Hz IEC 60947-4-1
Utilisation categoryAC-4 AC-1 AC-3
GV2P06KD09B7 — Protection
ParameterValue
Electrical durability (cycles)100000 cycles AC-3 440 V
Mechanical durability (cycles)100000 cycles
GV2P06KD09B7 — Mechanical
ParameterValue
Control typeRotary knob
Terminal connection typescrew clamp terminals 2 0.002...0.009 in² (1...6 mm²) solid screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) flexible without cable end screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) flexible with cable end
Terminal tightening torque15.05 lbf.in (1.7 N.m) screw clamp terminals
Width1.8 in (45 mm)
Height3.5 in (89 mm)
Depth3.8 in (97 mm)
GV2P06KD09B7 — Environmental
ParameterValue
Operating ambient temperature23...140 °F (-5...60 °C)
Storage ambient temperature-76...176 °F (-60...80 °C)
IP degree of protectionIP20 IEC 60529
Pollution degree3
GV2P06KD09B7 — Approvals
ParameterValue
StandardsIEC 60947-2 IEC 60947-4-1 VDE 0660 UL 508 NF C 79-130 CSA C22.2 VDE 0113 NF C 63-120 EN 60204 IEC 60947-1 NF C 63-650
GV2P06KD09B7 — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2

Product details

The Schneider Electric TeSys GV2P06KD09B7 is a direct on-line motor starter combining a 3-pole circuit breaker and contactor in one compact unit, rated at 1.6 A line current.

The 1.6 A line rated current sets the motor full-load amp threshold for overload protection; the magnetic trip is fixed at 22.5 A, meaning short-circuit protection clears fast on a hard fault while the thermal element handles sustained overloads. Utilisation categories AC-3 (squirrel-cage motor starting) and AC-4 (plugging/inching) are both covered, so this starter suits cyclic or reversing duty without derating. Electrical durability is rated at 100,000 cycles under AC-3 at 440 V, which aligns with typical conveyor or pump applications running a few cycles per hour.

Certified to IEC 60947-2, IEC 60947-4-1, UL 508, CSA C22.2, and VDE 0660, among others. The IP20 finger-safe enclosure (IEC 60529) and IK04 impact resistance are standard for panel-mounted gear. Flame retardance is V1 per UL 94, and glow-wire tested at 850 °C (IEC 60695-2-1).

Frequently asked questions

What compliance documentation is available for this starter?

The product carries IEC 60947-2, IEC 60947-4-1, UL 508, CSA C22.2, VDE 0660, and EN 60204 certifications. Flame retardance is V1 per UL 94, and glow-wire tested to 850 °C.

What is the breaking capacity at 400 V?

100 kA Icu at 400/415 V AC per IEC 60947-2, maintained across the full voltage range up to 690 V.

MPN