Skip to main content
Schneider Electric GV2P07KD09G7 — Molded Case Circuit Breakers (MCCB)

Schneider TeSys GV2P07KD09G7 Motor Starter, 2.5 A, 100 kA Br

MPNGV2P07KD09G7
Obsolete

Schneider Electric TeSys GV2P07KD09G7, motor starter, 2.5 A rated current, 100 kA breaking capacity at 400 V, 3-pole, direct on-line contactor.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2P07KD09G7 — Identification
ParameterValue
Product / component typeMotor starter
GV2P07KD09G7 — Mechanical
ParameterValue
Height3.5 in (89 mm)
Width1.8 in (45 mm)
Depth3.8 in (97 mm)
GV2P07KD09G7 — Electrical
ParameterValue
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 8 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltagePower circuit Power circuit 10 MOhm for signalling circuit
[Ui] rated insulation voltage690 V AC 50/60 Hz IEC 60947-2
GV2P07KD09G7 — Specifications
ParameterValue
Poles description3P
StandardsVDE 0113 CSA C22.2 EN 60204 IEC 60947-2 IEC 60947-4-1 NF C 79-130 NF C 63-120 NF C 63-650 VDE 0660 UL 508 IEC 60947-1

Product details

The Schneider Electric TeSys GV2P07KD09G7 is a 3-pole motor starter combining a contactor and thermal-magnetic overload relay in one compact unit, rated for 2.5 A line current. It's designed for direct on-line starting of three-phase motors up to 0.75 kW at 400/415 V AC, 1.1 kW at 500 V, or 1.5 kW at 690 V.

The 2.5 A rated current is the continuous thermal current (IEC 60947-4-1) — this governs the motor FLA it can carry without nuisance tripping. The magnetic trip is set at 33.5 A, so short-circuit protection clears fast on a locked-rotor or phase-to-phase fault. Utilisation categories AC-3 (squirrel-cage motors), AC-4 (plugging/inching), and AC-1 (resistive) cover the common motor-control duties; the 100,000-cycle electrical durability at AC-3 440 V gives a realistic service life for a production line running one start per minute over two shifts.

The 45 mm width (1.8 in) fits a standard 45 mm slot in a TeSys GV2 busbar or distribution block. IP20 finger-safe terminals (IEC 60529) mean it's safe for open-panel installation where only qualified personnel access the enclosure. Screw-clamp terminals accept 1 to 6 mm² solid or 1.5 to 6 mm² flexible wire; torque to 1.7 N·m.

Certified to UL 508, CSA C22.2, IEC 60947-2, IEC 60947-4-1, and EN 60204. The V1 flame retardance (UL 94) and 850 °C glow-wire resistance (IEC 60695-2-1) satisfy the fire-safety requirements for panel components in most industrial and commercial installations.

Frequently asked questions

What is the breaking capacity at 400 V?

100 kA Icu at 400/415 V AC 50/60 Hz per IEC 60947-2.

What motor power does this cover at 400 V?

0.75 kW at 400/415 V AC, 1.1 kW at 500 V, and 1.5 kW at 690 V.

What approvals does it carry?

UL 508, CSA C22.2, IEC 60947-2, IEC 60947-4-1, EN 60204, and VDE 0660.

MPN
GV2P07KD09G7