Skip to main content
Schneider Electric GV2P08AE11TQ — Molded Case Circuit Breakers (MCCB)

Schneider GV2P08AE11TQ TeSys Deca Motor Circuit Breaker, 4 A

MPNGV2P08AE11TQ
Active

Schneider Electric TeSys Deca GV2P08AE11TQ motor circuit breaker, 3-pole, 4 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 400 V AC, IP20.

$151.63Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2P08AE11TQ — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2P08AE11TQ — Mechanical
ParameterValue
Height89 mm
Width45 mm
Depth97 mm
GV2P08AE11TQ — Electrical
ParameterValue
[In] rated current4 A
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2 690 V conforming to IEC 60947-2 600 V conforming to CSA C22.2 No 14
GV2P08AE11TQ — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2P
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2

Product details

Motor circuit breaker for 1.1 kW at 400 V

The Schneider Electric GV2P08AE11TQ is a TeSys Deca motor circuit breaker rated at 4 A, sized for a 1.1 kW motor at 400...415 V AC. Rated for AC-3 duty (motor switching), it handles 100,000 electrical cycles at 415 V at full rated current. The utilisation category AC-3e is also listed, covering enhanced motor switching for higher-performance applications. Phase failure sensitivity is built in per IEC 60947-4-1, so the breaker trips if one phase drops out — a common failure mode that can burn out a motor running single-phase.

The 45 mm wide body fits standard enclosure cutouts, and the rotary handle provides local manual control. Screw-clamp terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule — torque to 1.7 N·m. The IP20 finger-safe enclosure suits panel-mount applications where the breaker is behind a locked door or cover. Built-in auxiliary contacts (1 NO + 1 NC) on the front allow remote status indication without adding a separate block.

Frequently asked questions

What are the key ratings for this motor circuit breaker?

Rated current 4 A, magnetic trip at 74 A, breaking capacity 100 kA Icu at 400 V AC. Suits a 1.1 kW motor at 400 V three-phase. Thermal-magnetic trip unit with phase failure sensitivity.

What compliance documentation does this part carry?

Listed to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Also complies with IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for fire resistance (960 °C glow-wire test).

What is the closest alternative within the TeSys Deca family?

Within the same GV2P series, the closest alternative would be a different current rating — the mechanical footprint and auxiliary contact arrangement are identical across the range. The deciding factor is the motor full-load current: select the GV2P variant whose rated current matches your motor nameplate.

MPN
GV2P08AE11TQ