Schneider Electric GV2P10AE11TQ — Miniature Circuit Breakers (MCB)

Schneider GV2P10AE11TQ TeSys GV2 Motor Circuit Breaker, 6.3

MPNGV2P10AE11TQ
Obsolete

Schneider Electric TeSys Deca GV2P10AE11TQ motor circuit breaker, 3-pole, thermal-magnetic, 6.3 A rated current, 100 kA breaking capacity at 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2P10AE11TQ — Identification
ParameterValue
Product nameTeSys GV2
Product rangeTeSys Deca
Product/component typeMotor circuit breaker
Device applicationMotor protection
GV2P10AE11TQ — Ratings
ParameterValue
Rated current (In)6.3 A
Poles configuration3P
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz conforming to IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1
GV2P10AE11TQ — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-1
Electrical durability (cycles)100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In
Mechanical durability (cycles)100000 cycles
GV2P10AE11TQ — Mechanical
ParameterValue
Control typeRotary handle
Terminal connection typePower circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end
Terminal tightening torque1.7 N.m - on screw clamp terminal
Width45 mm
Height89 mm
Depth97 mm
GV2P10AE11TQ — Environmental
ParameterValue
Operating ambient temperature-20...60 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
GV2P10AE11TQ — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2
GV2P10AE11TQ — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Product details

The Schneider GV2P10AE11TQ is a TeSys GV2 motor circuit breaker — a 3-pole thermal-magnetic device rated at 6.3 A continuous current, designed to protect motor circuits against overloads and short circuits. It's part of the TeSys Deca range, which is the current-generation platform for motor control and protection. Motor power ratings are 2.2 kW at 400/415 V, 3 kW at 500 V, and 4 kW at 690 V, all at 50/60 Hz. The magnetic trip threshold is set at 91 A — roughly 14.4 times the rated current — which keeps it from nuisance-tripping on motor inrush while still clearing a bolted fault quickly.

It fits in any standard control enclosure — horizontal or vertical orientation is fine. The rotary handle gives a clear visual indication of contact position, which helps during lockout/tagout procedures. IP20 finger-safe protection means it's suitable for enclosed panels where operators won't contact live parts. The IK04 impact rating handles the usual bumps during panel assembly.

Certified to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor + motor-starter standard), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 for North American installations. Also listed for use in appliance circuits per IEC/EN 60335-2-40 and IEC/EN 60335-1 Clause 30.2 — relevant if this goes into HVAC or refrigeration equipment.

Sourcing and procurement takeaway

This is a standard, active-production line item from the TeSys Deca family. It's specified into BOMs across panel shops and OEMs globally.

Frequently asked questions

What are the key ratings for this motor circuit breaker?

Rated current 6.3 A, breaking capacity 100 kA Icu at 400/415 V AC, motor power 2.2 kW at 400 V. Magnetic trip at 91 A. Thermal-magnetic trip unit with phase-failure sensitivity.

What standards does this part comply with?

Certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40 Annex JJ. Suitable for isolation per IEC 60947-1.

How does this mount in a panel?

Snaps onto 35 mm symmetrical DIN rail or mounts with two M4 screws. Accepts horizontal or vertical orientation. Power connections use screw clamp terminals accepting 1 to 6 mm² solid or 1.5 to 6 mm² flexible wire.

MPN
GV2P10AE11TQ