Part identification and key ratings
The Schneider Electric TeSys GV2P14KD09B7 is a direct on-line motor starter combining a 3-pole circuit breaker and a contactor in one unit, rated for a line current of 10 A. It is designed for motor control applications across utilisation categories AC-1 (resistive), AC-3 (squirrel-cage motor starting/stopping), and AC-4 (plugging/inching). Motor power capability spans 2.2 to 3 kW at 380 to 440 V three-phase, and 4 to 6 kW at 480 to 500 V three-phase, with a 24 V AC control coil.
This motor starter holds compliance with IEC 60947-2, IEC 60947-4-1, UL 508, CSA C22.2, VDE 0660, and EN 60204, covering overcurrent protection and motor controller requirements for North American and European installations. Pollution degree 3 rating suits industrial environments with conductive contamination.
IP20 finger-safe protection is provided per IEC 60529. Screw clamp terminals accept 1 to 6 mm² solid or stranded wire; tightening torque is 1.7 N·m. The rotary knob control allows manual on/off/reset without opening the enclosure.
Durability and environmental withstand
Rated for 100,000 electrical cycles under AC-3 at 440 V, and 100,000 mechanical cycles. Vibration resistance is 2 Gn (contactor open) and 4 Gn (closed) across 5 to 300 Hz; shock resistance is 10 Gn open and 15 Gn closed for 11 ms. Climatic withstand per IACS and protective treatment TH for tropical environments. Fire resistance tested to 850 °C per IEC 60695-2-1, with flame retardance V1 per UL 94.