Skip to main content
Schneider Electric GV2P14KD09G7 — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2P14KD09G7 Motor Starter, 10 A, 3 kW 400 V

MPNGV2P14KD09G7
Obsolete

Schneider Electric TeSys GV2P14KD09G7 motor starter, 3-pole, 10 A line rated current, 3 kW at 400 V AC, 100 kA breaking capacity, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2P14KD09G7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2P14KD09G7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Rated operational voltage (Ue)Power circuit Power circuit 10 MOhm for signalling circuit
Rated insulation voltage (Ui)690 V AC 50/60 Hz IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV IEC 60947-2
Network frequency50/60 Hz IEC 60947-4-1
Utilisation categoryAC-3 AC-1 AC-4 AC-3e
GV2P14KD09G7 — Protection
ParameterValue
Electrical durability (cycles)100000 cycles AC-3 440 V 100000 cycles AC-3e 440 V
Mechanical durability (cycles)100000 cycles
GV2P14KD09G7 — Mechanical
ParameterValue
Control typeRotary knob
Terminal connection typescrew clamp terminals 2 0.002...0.009 in² (1...6 mm²) solid screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) flexible without cable end screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) flexible with cable end
Terminal tightening torque15.05 lbf.in (1.7 N.m) screw clamp terminals
Width1.8 in (45 mm)
Height3.5 in (89 mm)
Depth3.8 in (97 mm)
GV2P14KD09G7 — Environmental
ParameterValue
Operating ambient temperature23...140 °F (-5...60 °C)
Storage ambient temperature-76...176 °F (-60...80 °C)
IP degree of protectionIP20 IEC 60529
Pollution degree3
GV2P14KD09G7 — Approvals
ParameterValue
StandardsIEC 60947-2 UL 508 VDE 0113 NF C 79-130 NF C 63-650 IEC 60947-1 CSA C22.2 NF C 63-120 IEC 60947-4-1 VDE 0660 EN 60204
GV2P14KD09G7 — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2

Product details

The Schneider Electric TeSys GV2P14KD09G7 is a 3-pole direct on-line motor starter rated for 10 A line current, combining a contactor and thermal-magnetic overload relay in one compact unit. It switches motor loads in AC-3 duty (squirrel-cage motors) up to 3 kW at 400/415 V AC and 5.5 kW at 690 V AC, and handles resistive loads in AC-1 as well as AC-4 reversing or inching applications.

Screw-clamp terminals accept 1 to 6 mm² solid or stranded wire; tighten to 1.7 N·m. The rotary knob provides local manual control — no separate pushbutton station needed for basic on/off.

Certified to IEC 60947-2 (circuit-breaker function), IEC 60947-4-1 (contactor/starter), UL 508, CSA C22.2, and VDE 0660. Pollution degree 3, IP20 finger-safe terminals, flame retardance V1 per UL 94, and glow-wire tested at 850 °C per IEC 60695-2-1. These approvals cover panel acceptance in North America, Europe, and most global markets.

Frequently asked questions

What is the breaking capacity of this motor starter?

The breaking capacity (Icu per IEC 60947-2) is 100 kA at 230/240 V, 400/415 V, and 440 V AC; 50 kA at 500 V AC; and 6 kA at 690 V AC.

What motor power does this starter cover?

At 400/415 V AC 3-phase, it covers motors from 0 to 3 kW. At 690 V AC, it covers up to 5.5 kW. Full power ranges for 100–120 V through 525–690 V are listed in the spec table.

What compliance documentation is available for this part?

The part carries IEC, UL, CSA, and VDE certifications as listed in the standards field. Specific RoHS/REACH declarations are typically provided by Schneider Electric upon request through our sourcing desk.

MPN
GV2P14KD09G7