Skip to main content
Schneider Electric GV2P14TQ — Miniature Circuit Breakers (MCB)

Schneider GV2P14TQ TeSys Deca Motor Circuit Breaker, 10 A

MPNGV2P14TQ
Obsolete

Schneider Electric TeSys Deca GV2P14TQ, motor circuit breaker, 3-pole, 10 A rated current, thermal-magnetic trip, 100 kA breaking capacity, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2P14TQ — Identification
ParameterValue
Product nameTeSys GV2
Product rangeTeSys Deca
Product/component typeMotor circuit breaker
Device applicationMotor protection
GV2P14TQ — Ratings
ParameterValue
Rated current (In)10 A
Poles configuration3P
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz conforming to IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1
GV2P14TQ — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-1
Electrical durability (cycles)100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In
Mechanical durability (cycles)100000 cycles
GV2P14TQ — Mechanical
ParameterValue
Control typeRotary handle
Terminal connection typePower circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end
Terminal tightening torque1.7 N.m - on screw clamp terminal
Width45 mm
Height89 mm
Depth97 mm
GV2P14TQ — Environmental
ParameterValue
Operating ambient temperature-20...60 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
GV2P14TQ — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2
GV2P14TQ — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Product details

The 45 mm width and 89 mm height fit standard enclosure layouts; depth is 97 mm. Rated IP20 finger-safe, so it's suited for enclosed panels where personnel access is controlled.

Rated 10 A continuous, with magnetic trip at 149 A — that's the instantaneous short-circuit pickup. Motor power ratings: 3 kW at 400/415 V, 5 kW at 500 V, 5.5 kW at 690 V. Electrical durability is 100,000 cycles at rated current in AC-3 duty — a solid service life for a motor-protection device.

Frequently asked questions

What are the key ratings for GV2P14TQ?

Rated current 10 A, magnetic trip at 149 A, breaking capacity 100 kA Icu at 400/415 V AC, motor power 3 kW at 400/415 V.

What compliance documentation does Schneider provide for GV2P14TQ?

The part is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. It also meets fire-resistance requirements per IEC 60695-2-11 at 960 °C.

MPN
GV2P14TQ