Skip to main content
Schneider Electric GV2P16AE11TQ — Molded Case Circuit Breakers (MCCB)

Schneider GV2P16AE11TQ TeSys Deca Motor Circuit Breaker, 14

MPNGV2P16AE11TQ
Active

Schneider Electric TeSys Deca GV2P16AE11TQ motor circuit breaker, 3-pole, 14 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 400 V AC.

$176.69Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2P16AE11TQ — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2P16AE11TQ — Mechanical
ParameterValue
Height89 mm
Width45 mm
Depth97 mm
GV2P16AE11TQ — Electrical
ParameterValue
[In] rated current14 A
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
GV2P16AE11TQ — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2P
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2

Product details

Rated for motor duty at 5.5 kW on a 400 V three-phase supply, it also covers 7.5 kW at 500 V and up to 11 kW at 690 V. The magnetic trip threshold sits at 253.4 A, and it includes phase-failure sensitivity per IEC 60947-4-1 — so a lost phase on the line side won't leave the motor single-phasing to destruction.

For most industrial installations fed from a 500 kVA or smaller transformer, that's more than enough headroom to avoid a cascading failure. The 6 kA rating at 690 V is a reminder that high-voltage faults are harder to interrupt; if your panel runs at 690 V, coordinate upstream accordingly. The 1 NO + 1 NC auxiliary contact set on the front lets you wire a status feedback to the PLC or a remote indicator without an add-on block. Electrical durability is rated at 100,000 cycles under AC-3 duty at 415 V, which is typical for a motor-starting profile — expect the mechanical life of 100,000 cycles to be the limiting factor if you're cycling it as a disconnect.

The 45 mm width (3-module footprint) fits standard enclosure cutouts. Power terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule — two conductors per terminal, which helps when daisy-chaining to a downstream contactor. Tightening torque is 1.7 N·m on the screw clamp terminals. IP20 finger-safe protection on the front, with an IK04 impact rating — adequate for enclosed panels where operators access the handle.

Certified to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (motor-starter standard), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 for North American installations. Also listed for IEC/EN 60335-2-40 (heat pump and air conditioner) and IEC/EN 60335-1 Clause 30.2 (glow-wire test at 960 °C per IEC 60695-2-11). Climatic withstand per IACS covers marine and humid environments.

Frequently asked questions

What are the key ratings I need to verify for fit?

The 14 A rated current (In) and the magnetic trip threshold of 253.4 A are the primary fit parameters. For motor duty, confirm the motor FLA falls within the 14 A setting range. The 100 kA breaking capacity at 400 V AC covers most industrial service entrances.

What compliance documentation is available for this part?

The GV2P16AE11TQ carries certifications to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. It also meets IEC/EN 60335-2-40 for heat-pump applications and has a 960 °C glow-wire test rating per IEC 60695-2-11.

What is the mounting footprint and terminal capacity?

It mounts on 35 mm DIN rail or panel with two M4 screws. Dimensions are 45 mm wide by 89 mm high by 97 mm deep. Power terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule, two conductors per terminal, at 1.7 N·m torque.

MPN
GV2P16AE11TQ