Skip to main content
Schneider Electric GV2P16KD25B7 — Molded Case Circuit Breakers (MCCB)

Schneider GV2P16KD25B7 TeSys Motor Starter, 14 A, 5.5 kW

MPNGV2P16KD25B7
Obsolete

Schneider TeSys GV2P16KD25B7 motor starter, direct-on-line contactor, 3-pole, 14 A rated, 5.5 kW at 400 V, 24 V AC coil, 100 kA breaking capacity.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2P16KD25B7 — Identification
ParameterValue
Product / component typeMotor starter
GV2P16KD25B7 — Mechanical
ParameterValue
Height3.5 in (89 mm)
Width1.8 in (45 mm)
Depth3.8 in (97 mm)
GV2P16KD25B7 — Electrical
ParameterValue
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2 42 kA Icu 500 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltagePower circuit Power circuit 10 MOhm for signalling circuit
[Ui] rated insulation voltage690 V AC 50/60 Hz IEC 60947-2
GV2P16KD25B7 — Specifications
ParameterValue
Poles description3P
StandardsCSA C22.2 IEC 60947-1 NF C 63-650 VDE 0660 VDE 0113 UL 508 NF C 63-120 NF C 79-130 IEC 60947-4-1 IEC 60947-2 EN 60204

Product details

The Schneider TeSys GV2P16KD25B7 is a 3-pole direct-on-line motor starter rated at 14 A line current, delivering 5.5 kW at 400/415 V AC and up to 11 kW at 690 V AC. The 24 V AC coil on this unit is standard for control circuits in panel builds.

The 45 mm width (1.8 in) slots into a standard 45 mm-wide DIN rail slot — no oversize footprint. Screw-clamp terminals accept 1 to 6 mm² solid or stranded wire; tighten to 1.7 N·m.

Carries UL 508, CSA C22.2, and IEC 60947-4-1 approvals — accepted across North American and IEC jurisdictions. Also listed to EN 60204 and VDE 0660. Pollution degree 3, IP20 finger-safe enclosure.

Frequently asked questions

What are the key ratings for this motor starter?

Rated line current 14 A. Motor power 5.5 kW at 400/415 V AC, up to 11 kW at 690 V AC. Breaking capacity 100 kA Icu at 400/415 V AC. Coil voltage 24 V AC. Three-pole, direct-on-line contactor type.

What compliance documentation is available?

The starter is certified to UL 508, CSA C22.2, IEC 60947-4-1, EN 60204, and VDE 0660. Flame retardance V1 per UL 94. Fire resistance at 850 °C per IEC 60695-2-1.

MPN
GV2P16KD25B7