Skip to main content
Schneider Electric GV2P21AE11TQ — Molded Case Circuit Breakers (MCCB)

Schneider TeSys GV2P21AE11TQ Motor Circuit Breaker, 23 A, 3P

MPNGV2P21AE11TQ
Obsolete

Schneider Electric TeSys Deca GV2P21AE11TQ motor circuit breaker, 3-pole, 23 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 230 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2P21AE11TQ — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2P21AE11TQ — Mechanical
ParameterValue
Height89 mm
Width45 mm
Depth97 mm
GV2P21AE11TQ — Electrical
ParameterValue
[In] rated current23 A
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
GV2P21AE11TQ — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2P
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2

Product details

The Schneider Electric TeSys GV2P21AE11TQ is a 3-pole motor circuit breaker rated at 23 A, part of the TeSys Deca range. It uses a thermal-magnetic trip unit, meaning the thermal element protects against sustained overloads and the magnetic element handles short-circuit faults. The magnetic tripping current is set at 341 A, so it clears fast on high faults without nuisance tripping on motor inrush.

Breaking capacity and fault handling

Rated breaking capacity (Icu) reaches 100 kA at 230/240 V AC, 50 kA at 400/415 V, and 20 kA at 440 V, all per IEC 60947-2. At the motor's common 400 V supply, 50 kA is high enough for most industrial panels with a transformer-fed fault level.

Motor protection specifics

Sized for motor loads: it switches 9 kW at 400/415 V, 11 kW at 500 V, and 18.5 kW at 690 V. The utilisation category includes AC-3 and AC-3e per IEC 60947-4-1, so it handles starting and stopping of squirrel-cage motors with occasional plugging or inching. Phase-failure sensitivity is built in, per IEC 60947-4-1, which protects a motor from single-phasing. Electrical durability is rated at 100,000 cycles at 415 V under AC-3 conditions.

Accepts power wiring via screw clamp terminals — up to two 6 mm² solid or 4 mm² flexible with ferrule. Tightening torque is 1.7 N·m. The front-mounted auxiliary contact block carries 1 NO + 1 NC, so you can wire a status feedback to the PLC without a separate contactor block.

IP20 rated, suitable for dry indoor panels. IK04 impact protection. Climatic withstand per IACS. Fire resistance tested to 960 °C per IEC 60695-2-11. Complies with EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40 Annex JJ. Suitable for isolation per IEC 60947-1.

Frequently asked questions

What are the key ratings for this motor circuit breaker?

Rated current 23 A, 3-pole, thermal-magnetic trip, magnetic trip at 341 A, breaking capacity 100 kA at 230 V, 50 kA at 400 V, motor power 9 kW at 400 V.

What standards does this part comply with?

It complies with EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC/EN 60335-2-40 Annex JJ, and IEC/EN 60335-1 Clause 30.2.

How does the GV2P21AE11TQ mount in a panel?

It clips onto a 35 mm symmetrical DIN rail or can be panel-mounted with two M4 screws. The width is 45 mm, depth 97 mm, height 89 mm.

MPN
GV2P21AE11TQ