Skip to main content
Schneider Electric GV2P21KD25B7 — Molded Case Circuit Breakers (MCCB)

Schneider Electric GV2P21KD25B7 TeSys motor starter, 23 A, 9

MPNGV2P21KD25B7
Obsolete

Schneider Electric TeSys GV2P21KD25B7 motor starter, 23 A rated current, 9 kW at 400 V, 100 kA breaking capacity, 3-pole, DIN rail mount, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2P21KD25B7 — Identification
ParameterValue
Product / component typeMotor starter
GV2P21KD25B7 — Mechanical
ParameterValue
Height3.5 in (89 mm)
Width1.8 in (45 mm)
Depth3.8 in (97 mm)
GV2P21KD25B7 — Electrical
ParameterValue
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 4 kA Icu 690 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltagePower circuit Power circuit 10 MOhm for signalling circuit
[Ui] rated insulation voltage690 V AC 50/60 Hz IEC 60947-2
GV2P21KD25B7 — Specifications
ParameterValue
Poles description3P
StandardsIEC 60947-1 NF C 79-130 VDE 0113 UL 508 CSA C22.2 EN 60204 NF C 63-650 VDE 0660 IEC 60947-2 IEC 60947-4-1 NF C 63-120

Product details

It is rated for continuous duty per IEC 60947-4-1 and carries a line rated current of 23 A, making it suitable for motor control applications up to 9 kW at 400/415 V AC and 11 kW at 500 V AC.

At 400/415 V the Icu is 50 kA, still substantial for most industrial distributions. The magnetic tripping current is set at 327 A, providing short-circuit protection coordinated with the thermal overload curve. IP20 finger-safe protection (IEC 60529) and IK04 impact resistance allow installation in control cabinets without additional shrouding.

This motor starter is designed for switching and protecting three-phase induction motors in applications like conveyors, pumps, fans, and compressors. The utilisation categories AC-3 (squirrel-cage motor starting) and AC-4 (plugging/inching) cover the majority of motor control duties, while AC-1 covers resistive loads. The 24 V AC coil voltage suits control circuits common in industrial panels.

Frequently asked questions

What are the key ratings for GV2P21KD25B7?

Rated current 23 A, motor power 9 kW at 400 V, breaking capacity 100 kA Icu at 230 V, magnetic trip 327 A, coil 24 V AC, 3-pole, DIN rail mount.

What compliance documentation is available for GV2P21KD25B7?

The part is certified to IEC 60947-1, IEC 60947-2, IEC 60947-4-1, UL 508, CSA C22.2, EN 60204, and VDE 0660. Flame retardance is V1 per UL 94; fire resistance tested at 850 °C per IEC 60695-2-1.

MPN