Skip to main content
Schneider Electric GV2P21KD25G7 — Molded Case Circuit Breakers (MCCB)

Schneider GV2P21KD25G7 TeSys motor starter, 23 A, 9 kW at 40

MPNGV2P21KD25G7
Obsolete

Schneider Electric TeSys GV2P21KD25G7, direct on-line motor starter, 3-pole, 23 A line rated current, 9 kW at 400 V AC, 100 kA breaking capacity, IP20, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2P21KD25G7 — Identification
ParameterValue
Product / component typeMotor starter
GV2P21KD25G7 — Mechanical
ParameterValue
Height3.5 in (89 mm)
Width1.8 in (45 mm)
Depth3.8 in (97 mm)
GV2P21KD25G7 — Electrical
ParameterValue
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 4 kA Icu 690 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltagePower circuit Power circuit 10 MOhm for signalling circuit
[Ui] rated insulation voltage690 V AC 50/60 Hz IEC 60947-2
GV2P21KD25G7 — Specifications
ParameterValue
Poles description3P
StandardsIEC 60947-1 NF C 79-130 VDE 0113 UL 508 CSA C22.2 EN 60204 NF C 63-650 VDE 0660 IEC 60947-2 IEC 60947-4-1 NF C 63-120

Product details

Motor starter for direct-on-line control

The Schneider Electric TeSys GV2P21KD25G7 is a direct on-line motor starter with a rotary knob control, rated for continuous duty per IEC 60947-4-1. It carries a line rated current of 23 A and delivers motor power of 9 kW at 400/415 V AC, 11 kW at 500 V AC, and 18.5 kW at 690 V AC — covering a motor power range of 7 to 11 kW at 380 to 440 V three-phase.

The IP20 finger-safe enclosure (IEC 60529) suits installation inside a control cabinet where the front panel is the operator interface. Screw-clamp terminals accept 1 to 6 mm² solid or 1.5 to 6 mm² flexible conductors; tighten to 1.7 N·m.

Compliant with IEC 60947-1, IEC 60947-2, IEC 60947-4-1, UL 508, CSA C22.2, EN 60204, and VDE 0660. Flame retardance V1 per UL 94; glow-wire tested to 850 °C per IEC 60695-2-1.

Frequently asked questions

What is the breaking capacity at 400 V?

50 kA Icu at 400/415 V AC per IEC 60947-2, which is the typical fault level for a 400 V industrial distribution panel.

What utilisation categories does it cover?

Rated for AC-3 (squirrel-cage motor starting), AC-4 (inching/plugging), and AC-1 (resistive load). The 23 A line rated current applies across these categories, but the electrical durability of 100,000 cycles at AC-3 440 V is the practical endurance figure for motor duty.

What is the magnetic tripping current?

327 A, which provides short-circuit protection for the motor branch circuit. The magnetic trip acts independently of the thermal overload.

MPN