Schneider Electric GV2RT05AE11TQ — Molded Case Circuit Breakers (MCCB)

Schneider TeSys GV2RT05AE11TQ Motor Circuit Breaker, 1 A, 10

MPNGV2RT05AE11TQ
Active

Schneider Electric TeSys Deca GV2RT05AE11TQ motor circuit breaker, 3-pole, thermal-magnetic, 1 A rated current, 100 kA breaking capacity at 400 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2RT05AE11TQ — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection Transformer
GV2RT05AE11TQ — Mechanical
ParameterValue
Height89 mm
Width45 mm
Depth78.5 mm
GV2RT05AE11TQ — Electrical
ParameterValue
[In] rated current1 A
Breaking capacity100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
GV2RT05AE11TQ — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2RT
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1

Product details

It uses a thermal-magnetic trip unit, with a rated current of 1 A and a magnetic tripping threshold of 22 A — meaning it protects against overloads (thermal) and short-circuits (magnetic) in one compact device. Rated for uninterrupted duty per IEC 60947-4-1, it is suitable for continuous motor loads.

IP20 finger-safe protection (IEC 60529) and IK04 impact resistance suit it for enclosed panel installation. Climatic withstand per IACS covers marine and humid environments.

Frequently asked questions

What are the key ratings for this motor circuit breaker?

Rated current 1 A, magnetic tripping at 22 A, breaking capacity 100 kA at 400 V AC (IEC 60947-2), suitable for motor protection up to 0.55 kW at 690 V AC.

What is the mounting method?

Snap-on 35 mm DIN rail or panel-mount with an adaptor plate. Accepts horizontal or vertical orientation.

Does it include auxiliary contacts?

Yes, it comes with 1 NO + 1 NC front-mounted auxiliary contacts built in.

MPN