Obsolete

Schneider Electric TeSys Deca GV2RT073 motor circuit breaker, 3-pole, thermal-magnetic, 2.5 A rated current, 100 kA breaking capacity at 400 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2RT073 — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection Transformer
GV2RT073 — Mechanical
ParameterValue
Height89 mm
Width45 mm
Depth78.5 mm
GV2RT073 — Electrical
ParameterValue
[In] rated current2.5 A
Breaking capacity100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
GV2RT073 — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2RT
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1

Product details

It uses a thermal-magnetic trip unit — the thermal element handles overloads, and the magnetic element (fixed at 51 A) clears short-circuits.

The thermal protection adjustment range is 1.6...2.5 A, so you set the dial to match the motor's full-load current. At the 2.5 A setting, this breaker covers motors rated 0.37 kW at 230 V or 0.75 kW at 400 V. The AC-3 utilisation category confirms it's rated for switching squirrel-cage motors — starting and stopping under load — with 100,000 electrical cycles at rated current. The 690 V rated insulation voltage and 6 kV impulse withstand voltage mean it's suitable for 400 V line-to-line systems with adequate margin.

Snaps onto 35 mm symmetrical DIN rail, or screws to a panel with an adaptor plate. The 45 mm width takes one standard modular slot. Spring-cage terminals on the power circuit accept 1...6 mm² solid or 1...4 mm² flexible with ferrule — no screw torque to verify, which speeds panel wiring. Mount horizontally or vertically; the IP20 finger-safe enclosure suits enclosed panels, not washdown zones.

Certified to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor-starter standard), so it qualifies as both a branch-circuit protective device and a motor-protective device. It's also suitability for isolation per IEC 60947-1 — meaning you can safely use the toggle as a visible disconnect. Climatic withstand per IACS covers marine and humid environments.

Frequently asked questions

What is the thermal adjustment range on this breaker?

The thermal protection adjustment range is 1.6 to 2.5 A. Set the dial to match the motor's full-load current within that window.

What breaking capacity does it have at 400 V?

100 kA Icu at 400/415 V AC, 50/60 Hz, per IEC 60947-2. This is the maximum short-circuit current it can safely interrupt at that voltage level.

What motor sizes does the 2.5 A setting cover?

At the 2.5 A setting, it covers a 0.37 kW motor at 230 V or a 0.75 kW motor at 400 V, both for motor protection with high peak current.

Does it mount on DIN rail?

Yes, it clips onto 35 mm symmetrical DIN rail. It can also be panel-mounted with an adaptor plate.