Skip to main content
Schneider Electric GV2RT163 — Molded Case Circuit Breakers (MCCB)

TeSys GV2RT163 Motor Circuit Breaker, 14 A, Thermal-Magnetic

MPNGV2RT163
Active

Schneider Electric TeSys Deca GV2RT163 motor circuit breaker, thermal-magnetic, 3-pole, 14 A rated current, spring terminals, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2RT163 — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection Transformer
GV2RT163 — Mechanical
ParameterValue
Height89 mm
Width45 mm
Depth78.5 mm
GV2RT163 — Electrical
ParameterValue
[In] rated current14 A
Breaking capacity100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
GV2RT163 — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2RT
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1

Product details

Its thermal-magnetic trip unit combines a bimetallic overload element adjustable from 9 to 14 A with a fixed magnetic trip set at 280 A, so it handles both sustained overloads and short-circuit faults in one package. Rated for uninterrupted duty per IEC 60947-4-1, it carries a 14 A continuous current and is listed for motor protection at 2.2 kW on 230 V AC up to 11 kW on 690 V AC. For transformer protection, the same unit covers 4 kW at 230/240 V AC up to 12.5 kW at 690 V AC. The breaking capacity (Icu) per IEC 60947-2 is 100 kA at 230 V AC, dropping to 15 kA at 400/415 V, 8 kA at 440 V, 6 kA at 500 V, and 3 kA at 690 V.

The 45 mm width (one standard modular unit) slots into a crowded enclosure without stealing extra space. Horizontal or vertical orientation is permitted. Power connections are spring terminals accepting 1 to 6 mm² solid or 1.5 to 4 mm² flexible wire (with or without ferrules). No screwdriver torque check needed — the spring cage holds the conductor firmly and resists vibration loosening. IP20 finger-safe protection on the front face; IK04 impact resistance. The enclosure is self-extinguishing at 960 °C per IEC 60695-2-11.

No substitution guesswork needed — this is the active, current-build part.

Altitude limited to 2000 m without derating. Climatic withstand conforms to IACS for marine and humid environments. Rated for 100,000 mechanical cycles and 100,000 electrical cycles under AC-3 duty at 415 V. Shock tested to 30 Gn for 11 ms, vibration to 5 Gn across 5–150 Hz — suitable for installation on machinery subject to moderate impact or continuous vibration. Power dissipation is 2.5 W per pole, so total heat load in the enclosure is 7.5 W at rated current.

Frequently asked questions

What are the key ratings for the GV2RT163?

Rated current is 14 A with a thermal adjustment range of 9 to 14 A. Magnetic trip is fixed at 280 A. Breaking capacity reaches 100 kA at 230 V AC and 15 kA at 400/415 V AC. It is a 3-pole thermal-magnetic motor circuit breaker rated for 690 V AC insulation voltage.

What compliance documentation does Schneider provide for the GV2RT163?

The GV2RT163 is certified to EN/IEC 60947-2 and EN/IEC 60947-4-1. It carries IP20 protection per IEC 60529, IK04 impact rating, and fire resistance at 960 °C per IEC 60695-2-11. It is suitable for isolation per IEC 60947-1. The manufacturer provides standard declarations of conformity for CE marking; specific RoHS and REACH documentation is available through the Schneider Electric compliance portal.

What is the GV2RT163's depth?

The depth is 78.5 mm. Width is 45 mm and height is 89 mm, so it occupies a single modular unit on a DIN rail.

What is the GV2RT163's range?

It belongs to the TeSys Deca range, specifically the GV2RT device short name series. This is the standard motor circuit breaker family from Schneider Electric for motor and transformer protection.

MPN