Skip to main content
Schneider Electric GV3L40

Schneider GV3L40 TeSys Deca Motor Circuit Breaker, 40A, 100k

MPNGV3L40
Active

Schneider TeSys Deca GV3L40, 3-pole motor circuit breaker, 40 A, 100 kA Icu at 230 V AC, IP20, rotary handle.

$60.96Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

GV3L40 key specifications
ParameterValue
Control typeRotary handle
Network typeAC
Product or component typeMotor circuit breaker
Climatic withstandIACS E10
Voltage690 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV IEC 60947-2
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz 50 kA Icu 400/415 V AC 50/60 Hz 50 kA Icu 440 V AC 50/60 Hz 12 kA Icu 500 V AC 50/60 Hz 6 kA Icu 690 V AC 50/60 Hz
Line rated current40 A
Magnetic tripping current560 A
[Ith] conventional free air thermal current40 A IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % 230/240 V AC 50/60 Hz 100 % 400/415 V AC 50/60 Hz 100 % 440 V AC 50/60 Hz 50 % 500 V AC 50/60 Hz 50 % 690 V AC 50/60 Hz

All specifications

GV3L40 additional specifications
ParameterValue
Motor power18.5 kW 400/415 V AC 50/60 Hz 22 kW 500 V AC 50/60 Hz 37 kW 690 V AC 50/60 Hz
Power dissipation per pole8 W
Network frequency50/60 Hz IEC 60947-2
Poles description3P
Rated dutyUninterrupted IEC 60947-4-1
Utilisation categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IP degree of protectionIP20 IEC 60529
Mounting positionHorizontal Vertical
Operating altitude9842.52 ft (3000 m)
ColorDark grey
Depth5.4 in (136 mm)
Width2.2 in (55 mm)
Height5.2 in (132 mm)
Product weight2.12 lb(US) (0.96 kg)
Electrical durability50000 cycles AC-3 415 V In
Mechanical durability50000 cycles
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-1:Clause 30.2 IEC/EN 60335-2-40:Annex JJ
RangeTeSys Deca
CategoryUS10I1122366
Fixing mode35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws)
Fire resistance1760 °F (960 °C) IEC 60695-2-11
Device short nameGV3L
Tightening torque44.3 lbf.in (5 N.m) screw clamp terminal
Device applicationMotor protection
Trip unit technologyMagnetic
Mechanical robustnessShocks 15 Gn for 11 ms contactor open Shocks 30 Gn for 11 ms contactor closed Vibrations 4 Gn, 5...300 Hz
Suitability for isolationYes IEC 60947-1
Ambient air temperature for storage-40...176 °F (-40...80 °C)
Ambient air temperature for operation-4...140 °F (-20...60 °C)

Product details

The Schneider GV3L40 is a 40 A motor circuit breaker from the TeSys Deca range, rated for motor protection with a magnetic trip set at 560 A and a breaking capacity of 100 kA at 230/240 V AC. That 40 A line current matches the full-load amps of a motor up to 18.5 kW at 400 V or 22 kW at 500 V — the power figures you care about for BOM matching. The magnetic trip at 560 A is instantaneous; it clears a bolted fault before the motor's thermal curve sees it, so you size the breaker so that trip is above the motor's starting inrush (typically 6–8× FLA). With 50 kA Icu at 400/415 V and 12 kA at 500 V, this breaker handles most industrial panel SCCR requirements without an upstream current-limiting fuse.

The rotary handle gives a clear on/off indication at the panel door — isolation suitability is marked per IEC 60947-1. Coil draw isn't an issue here since it's a thermal-magnetic breaker, not a contactor; the 8 W power dissipation per pole needs a little air movement if you pack several in a row. Wiring: screw-clamp terminals torque to 5 N·m, accepting conductors up to the rating. The IP20 means it's for enclosure use, not washdown.

Compliance documentation covers EN/IEC 60947-2 and -4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Fire resistance tested to 960 °C (IEC 60695-2-11). Climatic withstand per IACS. Storage temperature range -40 to 80 °C. These make it viable for machinery exports to North America and Europe without separate qualification runs.

Frequently asked questions

What are the key standards this breaker meets?

It complies with EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, covering motor protection and circuit breaker requirements for global markets.

What is the breaking capacity of the GV3L40 at 230 V?

At 230/240 V AC, the ultimate breaking capacity (Icu) is 100 kA. At 400/415 V it is 50 kA, at 500 V it is 12 kA, and at 690 V it is 6 kA.

What motor power does the GV3L40 support at 400 V?

At 400/415 V AC, it supports motors up to 18.5 kW. At 500 V it supports up to 22 kW, and at 690 V up to 37 kW.

MPN
GV3L40