Skip to main content
Schneider Electric GV3L651 — Miniature Circuit Breakers (MCB)

Schneider TeSys GV3L651 Motor Circuit Breaker, 65 A, 30 kW

MPNGV3L651
Obsolete

Schneider Electric TeSys Deca GV3L651 motor circuit breaker, 3-pole, 65 A rated current, magnetic trip, 30 kW at 400 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV3L651 — Identification
ParameterValue
Product nameTeSys GV3
Product rangeTeSys Deca
Product/component typeMotor circuit breaker
Device applicationMotor protection
GV3L651 — Ratings
ParameterValue
Rated current (In)65 A
Poles configuration3P
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz 50 kA Icu at 400/415 V AC 50/60 Hz 50 kA Icu at 440 V AC 50/60 Hz 12 kA Icu at 500 V AC 50/60 Hz 6 kA Icu at 690 V AC 50/60 Hz
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz conforming to IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1
GV3L651 — Protection
ParameterValue
Trip unit technologyMagnetic
Suitability for isolationYes conforming to IEC 60947-1
Electrical durability (cycles)50000 cycles for AC-3 at 415 V In
Mechanical durability (cycles)50000 cycles
GV3L651 — Mechanical
ParameterValue
Control typeRotary handle
Terminal tightening torque5 N.m - on screw clamp terminal
Width55 mm
Height114 mm
Depth136 mm
GV3L651 — Environmental
ParameterValue
Operating ambient temperature-20...60 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
GV3L651 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-1:Clause 30.2 IEC/EN 60335-2-40:Annex JJ
GV3L651 — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz 100 % at 400/415 V AC 50/60 Hz 100 % at 440 V AC 50/60 Hz 50 % at 500 V AC 50/60 Hz 50 % at 690 V AC 50/60 Hz

Product details

What the 65 A rating means for fit

The GV3L651 is a 3-pole motor circuit breaker from the TeSys Deca range, rated 65 A continuous (Ith and In). That 65 A figure governs the conductor sizing upstream — match it to a 65 A-rated feeder or downstream contactor. The magnetic trip is fixed at 910 A, so it clears short-circuit faults fast without nuisance tripping on motor inrush. Breaking capacity is 50 kA Icu at 400/415 V AC — that means it can safely interrupt a fault current up to 50 kA at typical 400 V industrial supply without welding contacts or cascading failure upstream. Motor power rating: 30 kW at 400/415 V, 37 kW at 500 V, 55 kW at 690 V. That's the load it can protect in AC-3 duty (squirrel-cage motors, starting and stopping under load). If your motor nameplate exceeds these kW figures at the corresponding voltage, step up to the next TeSys Deca frame.

The 55 mm width fits standard DIN-rail spacing — leaves room alongside a contactor for a compact motor starter combo. IP20 finger-safe terminals; install inside an enclosure rated for the environment. Screw-clamp terminals accept up to 5 N·m torque. Power dissipation is 8 W per pole — at full 65 A load the breaker sheds 24 W total, so account for that heat in your panel thermal budget, especially in a sealed cabinet.

Listed to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor/motor-starter standard), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1. That dual listing covers both the overcurrent protection and the motor-switching duty — one device, two standards. Also complies with IEC/EN 60335 for appliance applications.

Frequently asked questions

What is the breaking capacity at 400 V?

50 kA Icu at 400/415 V AC 50/60 Hz. That is the maximum short-circuit current it can safely interrupt at that voltage level.

What motor power does this cover?

30 kW at 400/415 V, 37 kW at 500 V, and 55 kW at 690 V, all in AC-3 duty. Match your motor's full-load kW at the operating voltage against these figures.

What standards does the GV3L651 comply with?

EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-1 Clause 30.2 and IEC/EN 60335-2-40 Annex JJ for appliance applications.

MPN
GV3L651