The GV4P02N6 is a 2 A, 3-pole motor circuit breaker from the TeSys Deca range, designed for motor protection on three-phase loads. The electronic thermal-magnetic trip unit provides overload and short-circuit protection, with magnetic tripping at 34 A. Phase failure sensitivity is built in per IEC 60947-4-1, eliminating the need for an external phase loss relay on the motor circuit. Breaking capacity reaches 100 kA Icu at 240 V AC (UL) and 65 kA at 240 V under UL, with 50 kA available at 380–415 V AC (IEC). This fault-interruption rating is unusually high for a 2 A frame, making the part suitable for installations with high available short-circuit current. Motor power ratings cover 0.25 kW through 1.5 kW at voltages from 400 V to 690 V AC, 50/60 Hz, in AC-3 utilization category. The AC-3 rating is the relevant load-heavy switching duty for starting and running induction motors.
Dimensions: 155 mm high, 81 mm wide, 165 mm deep. Front panel with rotary handle control. Accepts lug-ring terminals: power wiring up to 95 mm² with a tightening torque of 9 N·m, and control wiring from 1.5 to 10 mm² at 5 N·m. Connection pitch is 27 mm without spreaders, 35 mm with spreaders – factor this into cabinet layout. Operates in any position, altitude up to 5000 m. Pollution degree 3 for industrial environments. Mechanical durability 40,000 cycles; maximum operating rate 25 cycles per hour.
Certified to UL 60947-4-1, CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1 and EN/IEC 60947-2. Fire resistance tested to 960°C per IEC 60695-2-11. Suitability for isolation per IEC 60947-1 – the device can be used as a disconnecting means when locked off. Climatic withstand classification IACS covers damp heat. Color is Gray RAL 7016.