The Schneider Electric TeSys GV4 GV4P115B6 is a 3-pole motor circuit breaker rated at 115 A continuous, with electronic thermal-magnetic trip. It protects motors under IEC 60947-4-1 and UL 60947-4-1, with a magnetic trip fixed at 1955 A. It is phase failure sensitive and suitable for isolation.
Mounting & Connections
Dimensions: 6.1 x 3.2 x 6.5 in (155 x 81 x 165 mm). Accepts lug/ring terminals with a tightening torque of 79.7 lbf.in (9 N·m) for wire sizes up to 95 mm² (with spreaders at 35 mm pitch, or 27 mm without). Operating position is any orientation. IP40 front and IK07 impact protection. Pollution degree 3 rated.
Protection Performance
Trip technology is electronic thermal-magnetic with fixed magnetic trip at 1955 A. Electrical durability: 10,000 cycles at AC-3, In/2; 5,000 cycles at full In. Mechanical durability 40,000 cycles. Utilisation category A (IEC 60947-2) and AC-3 (IEC 60947-4-1). Suitable for isolation per IEC 60947-1. Phase failure sensitivity is standard.
Standards & Environment