GV4P12N6 key specifications
ParameterValue
Control typeRotary handle
Range of productTeSys GV4
Product or component typeMotor circuit breaker
Climatic withstandIACS E10
Voltage800 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947
Line rated current12.5 A
Magnetic tripping current212 A
[Ith] conventional free air thermal current115 A IEC 60947-4-1
Motor power3 kW 400...415 V AC 50/60 Hz 3 kW 500 V AC 50/60 Hz 4 kW 500 V AC 50/60 Hz 5.5 kW 660...690 V AC 50/60 Hz 7.5 kW 660...690 V AC 50/60 Hz 4 kW 400...415 V AC 50/60 Hz 5.5 kW 400...415 V AC 50/60 Hz 5.5 kW 500 V AC 50/60 Hz 7.5 kW 500 V AC 50/60 Hz 9 kW 660...690 V AC 50/60 Hz 11 kW 660...690 V AC 50/60 Hz

All specifications

GV4P12N6 additional specifications
ParameterValue
Power dissipation per pole4.6 W
Poles description3P
Phase failure sensitivityYes IEC 60947-4-1
Rated dutyContinuous IEC 60947-4-1
Utilisation categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IK degree of protectionIK07 IEC 62262
IP degree of protectionIP40 IEC 60529
Connection pitch1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders
Connections - terminalsLugs-ring terminals
Pollution degree3
Operating altitude5000 m
ColorGray RAL 7016)
Depth6.5 in (165 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical durability40000 cycles AC-3 440 V In/2 40000 cycles AC-3 440 V In
Mechanical durability40000 cycles
StandardsCSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2
RangeTeSys Deca
CategoryUS10I1122365
Fire resistance1760 °F (960 °C) IEC 60695-2-11
Device short nameGV4P
Tightening torque79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)
Device applicationMotor protection
Operating positionAny position
Trip unit technologyElectronic Thermal-magnetic
Mechanical robustnessVibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27
Maximum operating rate25 cyc/h
Suitability for isolationYes IEC 60947-1
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)

Product details

What it is and fit

The GV4P12N6 is a 12.5 A motor circuit breaker from the TeSys Deca range, designed for motor protection with an electronic thermal-magnetic trip unit. It handles AC-3 switching duty up to that current and offers a breaking capacity of 100 kA at 240 V AC (UL) and 50 kA at 415 V (IEC).

Dimensions are 3.2 in wide by 6.1 in tall by 6.5 in deep, fitting a standard 27 mm pitch on the busbar (35 mm with spreaders). Terminals accept lugs or ring terminals; tightening torque is 9 Nm for the main circuit (95 mm² max) and 5 Nm for the control circuit (10 mm² max). Color is Gray RAL 7016.

Protection features

The trip unit provides electronic overload protection with phase failure sensitivity (IEC 60947-4-1) and magnetic short-circuit pickup at 212 A. Suitable for isolation per IEC 60947-1. Power dissipation is 4.6 W per pole, important for enclosure thermal management. IP40 enclosure, IK07 impact resistance.

Frequently asked questions

What is GV4P12N6's listed color?

Gray RAL 7016.

What is GV4P12N6's listed depth?

6.5 in (165 mm).

What compliance documentation does this brand provide for GV4P12N6?

It complies with UL 60947-4-1, CSA C22.2 No 60947-4-1, and EN/IEC 60947-4-1 for motor circuit breakers.