Skip to main content
Schneider Electric GV4P50B

Schneider GV4P50B TeSys GV4 50A Motor Circuit Breaker, 3P

MPNGV4P50B
Active

Schneider Electric TeSys Deca GV4P50B motor circuit breaker, 3-pole, 50 A, rotary handle, gray RAL 7016 enclosure.

$83.82Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

GV4P50B key specifications
ParameterValue
Control typeRotary handle
Range of productTeSys GV4
Product or component typeMotor circuit breaker
Climatic withstandIACS E10
Voltage800 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA 208Y/120 V AC 50/60 Hz UL 60947 35 kA 240 V AC 50/60 Hz UL 60947 18 kA 480Y/277 V AC 50/60 Hz UL 60947 14 kA 600Y/347 V AC 50/60 Hz UL 60947
Line rated current50 A
Magnetic tripping current850 A
[Ith] conventional free air thermal current115 A IEC 60947-4-1
Motor power11 kW 400...415 V AC 50/60 Hz 15 kW 500 V AC 50/60 Hz 18.5 kW 660...690 V AC 50/60 Hz 15 kW 400...415 V AC 50/60 Hz 18.5 kW 400...415 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 500 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 22 kW 660...690 V AC 50/60 Hz 30 kW 660...690 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz

All specifications

GV4P50B additional specifications
ParameterValue
Power dissipation per pole4.6 W
Poles description3P
Phase failure sensitivityYes IEC 60947-4-1
Rated dutyContinuous IEC 60947-4-1
Utilisation categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IK degree of protectionIK07 IEC 62262
IP degree of protectionIP40 IEC 60529
Connections - terminalsEverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible
Pollution degree3
Operating altitude5000 m
ColorGray RAL 7016)
Depth6.5 in (165 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical durability20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In
Mechanical durability40000 cycles
StandardsCSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2
RangeTeSys Deca
CategoryUS10I1122365
Fire resistance1760 °F (960 °C) IEC 60695-2-11
Device short nameGV4P
Tightening torque79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)
Device applicationMotor protection
Operating positionAny position
Trip unit technologyThermal-magnetic Electronic
Mechanical robustnessVibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27
Maximum operating rate25 cyc/h
Suitability for isolationYes IEC 60947-1
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)

Product details

The Schneider Electric GV4P50B is a 3-pole motor circuit breaker from the TeSys GV4 series, rated 50 A continuous for motor protection in accordance with IEC/UL 60947-4-1. It belongs to the TeSys Deca range and provides a rotary handle operation for local isolation.

Breaking capacity and duty ratings

Breaking capacity reaches 50 kA at 240 V AC under UL 60947, and 25 kA at 415 V per IEC 60947-2. For 480Y/277 V systems, the symmetrical interrupting rating is 18 kA. The magnetic trip point is fixed at 850 A, covering motor starting inrush without nuisance trips on AC-3 duty. Electrical durability is rated at 20,000 cycles at AC-3 440 V with half rated current, and 10,000 cycles at full rated current. Mechanical endurance is 40,000 cycles. Maximum operating rate is 25 cycles per hour.

Dimensions are 81 mm wide, 155 mm high, 165 mm deep. The enclosure is IP40 with IK07 impact resistance. Pollution degree 3 rated, suitable for industrial panel environments without additional derating for altitude up to 5000 m. Terminals accept solid or flexible copper: top 1.5–70 mm² solid, bottom 2.5–95 mm² solid. Tightening torque is 9 N·m for main conductors and 5 N·m for control wiring.

Frequently asked questions

What is GV4P50B's listed depth?

Depth is 6.5 inches (165 mm).

What compliance documentation does Schneider provide for GV4P50B?

The GV4P50B is certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2. It also carries fire resistance tested to IEC 60695-2-11 at 960 °C.

MPN
GV4P50B