Skip to main content
Schneider Electric GV4P50N

Schneider Electric GV4P50N TeSys Deca Motor Circuit Breaker,

MPNGV4P50N
Active

Schneider Electric TeSys Deca GV4P50N, motor circuit breaker, 3P, 50 A, 100 kA breaking at 240 V, Gray RAL 7016.

$106.68Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

GV4P50N key specifications
ParameterValue
Control typeRotary handle
Range of productTeSys GV4
Product or component typeMotor circuit breaker
Climatic withstandIACS E10
Voltage800 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947
Line rated current50 A
Magnetic tripping current850 A
[Ith] conventional free air thermal current115 A IEC 60947-4-1
Motor power11 kW 400...415 V AC 50/60 Hz 15 kW 500 V AC 50/60 Hz 18.5 kW 660...690 V AC 50/60 Hz 15 kW 400...415 V AC 50/60 Hz 18.5 kW 400...415 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 500 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 22 kW 660...690 V AC 50/60 Hz 30 kW 660...690 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz

All specifications

GV4P50N additional specifications
ParameterValue
Power dissipation per pole4.6 W
Poles description3P
Phase failure sensitivityYes IEC 60947-4-1
Rated dutyContinuous IEC 60947-4-1
Utilisation categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IK degree of protectionIK07 IEC 62262
IP degree of protectionIP40 IEC 60529
Connections - terminalsEverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible
Pollution degree3
Operating altitude5000 m
ColorGray RAL 7016)
Depth6.5 in (165 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical durability20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In
Mechanical durability40000 cycles
StandardsCSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2
RangeTeSys Deca
CategoryUS10I1122365
Fire resistance1760 °F (960 °C) IEC 60695-2-11
Device short nameGV4P
Tightening torque79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)
Device applicationMotor protection
Operating positionAny position
Trip unit technologyElectronic Thermal-magnetic
Mechanical robustnessVibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27
Maximum operating rate25 cyc/h
Suitability for isolationYes IEC 60947-1
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)

Product details

The GV4P50N is a 3-pole motor circuit breaker from the TeSys Deca range, rated 50 A continuous with an electronic thermal-magnetic trip unit. The gray RAL 7016 enclosure carries EverLink BTR screw terminals rated for 95 mm² solid on the line side and 70 mm² flexible on the load side.

Physical Verification Points

Show me the date code when it lands. The IP40 housing and IK07 impact rating are standard for this industrial class; the rotary handle control and phase-failure sensitivity per IEC 60947-4-1 are also present. Torque spec on the main terminals is 9 N·m—if the mark looks off, that's a red flag. Remarked parts hide in plain sight; verify the UL and CSA logos match the spec table.

Schneider's lifecycle stage for this unit is current production—no last-time-buy notice or end-of-life date has been issued. This means standard supply chain availability, but always confirm the date code on incoming inspection.

Frequently asked questions

What color is the GV4P50N housing?

The enclosure is Gray RAL 7016.

What is the depth of the GV4P50N?

The depth is 6.5 inches (165 mm).

What compliance certifications does the GV4P50N carry?

It is certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2.

What is the rated breaking capacity of the GV4P50N at 240 V?

The breaking capacity is 100 kA Icu at 220...240 V AC per IEC 60947-2.

MPN
GV4P50N