The GV4PB03S is a TeSys Deca motor circuit breaker, rated 3.5 A continuous on a 3-pole frame. It packs a 100 kA SCCR at 240 V AC under UL 489, with a symmetrical breaking capacity up to 120 kA Icu at 220/240 V under IEC 60947-2. That places it in a class above typical 3.5 A motor protectors—designed for panels where fault current levels would otherwise force a larger frame or upstream fuse coordination.
Key ratings
The electronic thermal-magnetic trip unit offers both overload and short-circuit protection, with a magnetic trip threshold set at 60 A. The 25 cycles per hour maximum operating rate fits standard motor starting duty. For panel builders, the EverLink screw terminals accept up to 95 mm² (rigid) on the bottom, and the IP40 front face with IK07 impact resistance suits enclosed installations.
Current production, with a broad base of international approvals—UL 489, CSA C22.2 No 5, and EN/IEC 60947-4-1—that smooth regional acceptance without custom variants. Sourced to order through standard distribution; supply-demand balance is stable for this TeSys Deca platform.