Part identification and key ratings
The Schneider GV4PE02N is a TeSys Deca-series motor circuit breaker with a line rated current of 2 A, the smallest rating in the GV4PE family, suited for protecting fractional-horsepower motors from 0.25 kW at 400 V up to 1.5 kW at 690 V. Three-pole design with electronic thermal-magnetic trip, combining thermal overload protection with instantaneous magnetic trip set at 34 A.
Rated for continuous duty per IEC 60947-4-1, with electrical durability of 40,000 cycles at AC-3 (In) and mechanical durability of 40,000 cycles, adequate for typical machine-tool duty cycles at a maximum operating rate of 25 cycles per hour. Phase failure sensitivity per IEC 60947-4-1 ensures the breaker trips on loss of one phase, protecting the motor from single-phasing – a standard feature in modern motor-protective devices. IP40 rated, IK07 impact resistance, and pollution degree 3 allow placement in standard panel environments; operates in any position and up to 5000 m altitude.