Skip to main content
Schneider Electric GV4PE03N

Schneider GV4PE03N Motor Circuit Breaker, 3.5 A, TeSys Deca

MPNGV4PE03N
Active

Schneider Electric TeSys GV4 motor circuit breaker, GV4PE03N, 3.5 A rated current, 3-pole, electronic thermal-magnetic trip, IP40, gray RAL 7016.

$770.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

GV4PE03N key specifications
ParameterValue
Control typeToggle
Range of productTeSys GV4
Product or component typeMotor circuit breaker
Climatic withstandIACS E10
Voltage800 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947
Line rated current3.5 A
Magnetic tripping current59 A
[Ith] conventional free air thermal current115 A IEC 60947-4-1
Motor power0.55 kW 400...415 V AC 50/60 Hz 0.75 kW 400...415 V AC 50/60 Hz 0.75 kW 500 V AC 50/60 Hz 1.1 kW 500 V AC 50/60 Hz 1.1 kW 660...690 V AC 50/60 Hz 1.5 kW 660...690 V AC 50/60 Hz 1.5 kW 500 V AC 50/60 Hz 2.2 kW 660...690 V AC 50/60 Hz 1.1 kW 400...415 V AC 50/60 Hz 1.5 kW 400...415 V AC 50/60 Hz

All specifications

GV4PE03N additional specifications
ParameterValue
Power dissipation per pole4.6 W
Poles description3P
Phase failure sensitivityYes IEC 60947-4-1
Rated dutyContinuous IEC 60947-4-1
Utilisation categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IK degree of protectionIK07 IEC 62262
IP degree of protectionIP40 IEC 60529
Connections - terminalsEverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible
Pollution degree3
Operating altitude5000 m
ColorGray RAL 7016)
Depth4.6 in (116 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical durability40000 cycles AC-3 440 V In/2 40000 cycles AC-3 440 V In
Mechanical durability40000 cycles
StandardsCSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2
RangeTeSys Deca
CategoryUS10I1122365
Fire resistance1760 °F (960 °C) IEC 60695-2-11
Device short nameGV4PE
Tightening torque79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)
Device applicationMotor protection
Operating positionAny position
Trip unit technologyElectronic Thermal-magnetic
Mechanical robustnessVibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27
Maximum operating rate25 cyc/h
Suitability for isolationYes IEC 60947-1
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)

Product details

Motor circuit breaker for 3.5 A protection

The GV4PE03N is a 3-pole motor circuit breaker from the TeSys Deca range, rated 3.5 A continuous. It sits between the supply and a motor up to 0.75 kW at 400 V AC (or 1.5 kW at 500 V). The electronic thermal-magnetic trip unit gives both overload and short-circuit protection; magnetic trip kicks in at 59 A. Phase failure sensitivity is built in per IEC 60947-4-1, so it catches a lost phase before the motor cooks. That covers most industrial panels with high fault current; you can use it in a line-up without worrying about series rating. For 480Y/277 V UL systems it still holds 35 kA.

Climatic withstand meets IACS; operating altitude up to 5000 m. The EverLink BTR screw terminals accept solid copper up to 95 mm² bottom / 70 mm² top, or flexible up to 70 mm² bottom / 50 mm² top. Tightening torque is 9 N·m for the power terminals. IP40 front face keeps dust out; IK07 impact resistance. Toggle control with 25 cycles/hour max operating rate. 40000 mechanical cycles, same for electrical at AC-3. Fits any mounting position.

Frequently asked questions

What color is the GV4PE03N?

The enclosure color is gray RAL 7016.

What is the depth of this motor circuit breaker?

Depth is 4.6 in (116 mm).

What compliance documentation is available for the GV4PE03N?

It is certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, and EN/IEC 60947-4-1 and 60947-2. Fire resistance tested to 960 °C (IEC 60695-2-11).

MPN