Schneider Electric GV4PE80N6

Schneider GV4PE80N6 TeSys Deca Motor Circuit Breaker, 80A, 3

MPNGV4PE80N6
Active

Schneider Electric TeSys Deca GV4PE80N6 motor circuit breaker, 3-pole, 80 A, thermal-magnetic/electronic trip, gray RAL 7016.

$935.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

GV4PE80N6 key specifications
ParameterValue
Control typeToggle
Range of productTeSys GV4
Product or component typeMotor circuit breaker
Climatic withstandIACS E10
Voltage800 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947
Line rated current80 A
Magnetic tripping current1360 A
[Ith] conventional free air thermal current115 A IEC 60947-4-1
Motor power37 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz 55 kW 660...690 V AC 50/60 Hz 30 kW 400...415 V AC 50/60 Hz 37 kW 500 V AC 50/60 Hz

All specifications

GV4PE80N6 additional specifications
ParameterValue
Power dissipation per pole4.6 W
Poles description3P
Phase failure sensitivityYes IEC 60947-4-1
Rated dutyContinuous IEC 60947-4-1
Utilisation categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IK degree of protectionIK07 IEC 62262
IP degree of protectionIP40 IEC 60529
Connection pitch1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders
Connections - terminalsLugs-ring terminals
Pollution degree3
Operating altitude5000 m
ColorGray RAL 7016)
Depth4.6 in (116 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical durability14000 cycles AC-3 440 V In/2 7000 cycles AC-3 440 V In
Mechanical durability40000 cycles
StandardsCSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2
RangeTeSys Deca
CategoryUS10I1122365
Fire resistance1760 °F (960 °C) IEC 60695-2-11
Device short nameGV4PE
Tightening torque79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)
Device applicationMotor protection
Operating positionAny position
Trip unit technologyThermal-magnetic Electronic
Mechanical robustnessVibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27
Maximum operating rate25 cyc/h
Suitability for isolationYes IEC 60947-1
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)

Product details

The GV4PE80N6 is a 3-pole motor circuit breaker from the TeSys Deca range, rated 80 A continuous for AC-3 motor protection per IEC 60947-4-1. Its trip unit merges thermal-magnetic and electronic elements, providing phase-failure sensitivity per IEC 60947-4-1.

Lifecycle stage is 'current' — active in production.

With an interrupting capacity of 100 kA at 240 V AC (IEC 60947-2) and 50 kA at 415 V, the GV4PE80N6 provides substantial SCCR headroom for most industrial distribution panels — the 100 kA figure at 240 V is the high end for a 3-pole motor circuit breaker in this frame.

Dimensions: width 81 mm, depth 116 mm, height 155 mm. IP40 enclosure protection, IK07 impact resistance. Operating position any; altitude 5000 m max. Connection via lugs/ring terminals. Tightening torque 9 N·m for conductors up to 95 mm² (0.02–0.1 in²), 5 N·m for control wires 1.5–10 mm² — the 79.7 lbf·in value for the main power circuit is within spec.

Mechanical endurance: 40,000 operations. Electrical endurance at AC-3 440 V: 14,000 cycles at In/2, 7,000 cycles at In. Maximum operating rate 25 cycles per hour.

Frequently asked questions

What is GV4PE80N6's listed color?

Gray RAL 7016.

What is GV4PE80N6's listed depth?

4.6 in (116 mm).

MPN