Skip to main content
Schneider Electric GV4PE80S6

Schneider GV4PE80S6 TeSys GV4, 80A Motor Circuit Breaker

MPNGV4PE80S6
Active

Schneider Electric TeSys GV4 motor circuit breaker, GV4PE80S6, 80 A, 3 poles, electronic thermal-magnetic trip, breaking capacity 120 kA Icu at 240 V AC, gray RAL 7016.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

GV4PE80S6 key specifications
ParameterValue
Control typeToggle
Range of productTeSys GV4
Product or component typeMotor circuit breaker
Climatic withstandIACS E10
Voltage800 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 100 kA 208Y/120 V AC 50/60 Hz UL 60947 100 kA 240 V AC 50/60 Hz UL 60947 65 kA 480Y/277 V AC 50/60 Hz UL 60947 10 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA 600Y/347 V AC 50/60 Hz UL 60947
Line rated current80 A
Magnetic tripping current1360 A
[Ith] conventional free air thermal current115 A IEC 60947-4-1
Motor power37 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz 55 kW 660...690 V AC 50/60 Hz 30 kW 400...415 V AC 50/60 Hz 37 kW 500 V AC 50/60 Hz

All specifications

GV4PE80S6 additional specifications
ParameterValue
Power dissipation per pole4.6 W
Poles description3P
Phase failure sensitivityYes IEC 60947-4-1
Rated dutyContinuous IEC 60947-4-1
Utilisation categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IK degree of protectionIK07 IEC 62262
IP degree of protectionIP40 IEC 60529
Connection pitch1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders
Connections - terminalsLugs-ring terminals
Pollution degree3
Operating altitude5000 m
ColorGray RAL 7016)
Depth4.6 in (116 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical durability14000 cycles AC-3 440 V In/2 7000 cycles AC-3 440 V In
Mechanical durability40000 cycles
StandardsCSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2
RangeTeSys Deca
CategoryUS10I1122365
Fire resistance1760 °F (960 °C) IEC 60695-2-11
Device short nameGV4PE
Tightening torque79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)
Device applicationMotor protection
Operating positionAny position
Trip unit technologyElectronic Thermal-magnetic
Mechanical robustnessVibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27
Maximum operating rate25 cyc/h
Suitability for isolationYes IEC 60947-1
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)

Product details

Integrator's Note: 80 A, 3-Pole Motor Circuit Breaker for TeSys Deca

The GV4PE80S6 is a 3-pole motor circuit breaker from the TeSys GV4 range, rated 80 A line current. Its electronic thermal-magnetic trip provides motor protection with phase failure sensitivity per IEC 60947-4-1. Mounts on DIN rail, IP40 front face, IK07 impact resistance, gray RAL 7016 enclosure. Continuous duty rated, suitable for isolation per IEC 60947-1.

Protection and Durability

Magnetic tripping is fixed at 1360 A; overload protection is handled by the electronic trip unit, adjustable via TeSys Deca accessories. Electrical durability: 14,000 cycles under AC-3 at 440 V at half load (In/2), 7,000 cycles at full load. Mechanical durability: 40,000 cycles. Maximum operating rate: 25 cycles per hour. Power dissipation per pole is 4.6 W — include in panel thermal calculations.

Certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2. Fire resistance tested at 960 °C per IEC 60695-2-11; rated for pollution degree 3 and operating altitude up to 5000 m.

Frequently asked questions

What is the listed color?

Gray RAL 7016.

What is the depth?

4.6 in (116 mm).

What compliance documentation is available?

Meets UL 60947-4-1, CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2.

MPN