Motor protection for the TeSys Deca frame
The GV4PEM02N6 is a 3-pole motor circuit breaker on the TeSys Deca frame, line rated for 2 A continuous. The electronic thermal-magnetic trip unit combines adjustable overload protection with a fixed magnetic pickup of 34 A for short-circuit clearance. Rated for AC-3 duty (motors), it delivers 100 kA Icu breaking capacity at 240 V AC and 50 kA at 415 V AC per IEC 60947-2. For UL 60947 listings, 65 kA at 240 V and 35 kA at 480Y/277 V. Phase failure sensitivity is included; the breaker isolates the motor on single-phasing conditions. Continuous duty rated per IEC 60947-4-1.
Physical integration and environmental ratings
Enclosure is IP40 with IK07 mechanical impact protection, gray RAL 7016. Depth 4.6 in (116 mm), width 3.2 in (81 mm), height 6.1 in (155 mm). Pollution degree 3, operating altitude up to 5000 m. Connection pitch is 1.06 in (27 mm) without spreaders, 1.4 in (35 mm) with. Terminals accept lugs or ring terminals; tightening torque for the power circuit is 79.7 lbf·in (9 N·m) for 16–95 mm² conductors, 44.3 lbf·in (5 N·m) for 1.5–10 mm². Mechanical and electrical durability: 40,000 cycles for both (AC-3 at 440 V In). Maximum operating rate 25 cycles/h. Vibration and shock tested per IEC 60068-2-6 and -2-27.
The GV4PEM02N6 is listed under UL 60947-4-1 and CSA C22.2 No 60947-4-1, plus EN/IEC 60947-4-1 and EN/IEC 60947-2. Fire resistance rated to 1760 °F (960 °C) per IEC 60695-2-11. This is a current-production part (lifecycle stage: current). Submit an inquiry for lead time and pricing.