The Schneider GV4PEM03N is a 3-pole motor circuit breaker from the TeSys GV4 range, rated 3.5 A with a thermal-magnetic electronic trip unit.
Rated current of 3.5 A aligns with motor full-load currents for 0.55 kW to 2.2 kW motors at 400 V to 690 V. The magnetic trip set at 59 A provides short-circuit protection without nuisance tripping on startup. Breaking capacity of 100 kA at 240 V AC covers most industrial service-entrance fault levels; at 480 V it still holds 35 kA under UL 60947. That keeps SCCR coordination simple in a 480Y/277 V panel. Rated for continuous duty, category A (IEC 60947-2), AC-3 switching (IEC 60947-4-1). Phase failure sensitivity built in per IEC 60947-4-1 — no external relay needed for three-phase motor protection. Pollution degree 3, IP40 enclosure, IK07 impact resistance.