GV4PEM03N key specifications
ParameterValue
Control typeToggle
Range of productTeSys GV4
Product or component typeMotor circuit breaker
Climatic withstandIACS E10
Voltage800 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947
Line rated current3.5 A
Magnetic tripping current59 A
[Ith] conventional free air thermal current115 A IEC 60947-4-1
Motor power0.55 kW 400...415 V AC 50/60 Hz 0.75 kW 400...415 V AC 50/60 Hz 0.75 kW 500 V AC 50/60 Hz 1.1 kW 500 V AC 50/60 Hz 1.1 kW 660...690 V AC 50/60 Hz 1.5 kW 660...690 V AC 50/60 Hz 1.5 kW 500 V AC 50/60 Hz 2.2 kW 660...690 V AC 50/60 Hz 1.1 kW 400...415 V AC 50/60 Hz 1.5 kW 400...415 V AC 50/60 Hz

All specifications

GV4PEM03N additional specifications
ParameterValue
Power dissipation per pole4.6 W
Poles description3P
Phase failure sensitivityYes IEC 60947-4-1
Rated dutyContinuous IEC 60947-4-1
Utilisation categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IK degree of protectionIK07 IEC 62262
IP degree of protectionIP40 IEC 60529
Connections - terminalsEverLink BTR screw connectors top) 1 0.002...0.1 in² (1.5...70 mm²) - solid EverLink BTR screw connectors top) 1 0.002...0.08 in² (1.5...50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004...0.1 in² (2.5...70 mm²) - flexible
Pollution degree3
Operating altitude5000 m
ColorGray RAL 7016)
Depth4.6 in (116 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical durability40000 cycles AC-3 440 V In/2 40000 cycles AC-3 440 V In
Mechanical durability40000 cycles
StandardsCSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2
RangeTeSys Deca
CategoryUS10I1122365
Fire resistance1760 °F (960 °C) IEC 60695-2-11
Device short nameGV4PEM
Tightening torque79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)
Device applicationMotor protection
Operating positionAny position
Trip unit technologyThermal-magnetic Electronic
Mechanical robustnessVibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27
Maximum operating rate25 cyc/h
Suitability for isolationYes IEC 60947-1
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)

Product details

The Schneider GV4PEM03N is a 3-pole motor circuit breaker from the TeSys GV4 range, rated 3.5 A with a thermal-magnetic electronic trip unit.

Rated current of 3.5 A aligns with motor full-load currents for 0.55 kW to 2.2 kW motors at 400 V to 690 V. The magnetic trip set at 59 A provides short-circuit protection without nuisance tripping on startup. Breaking capacity of 100 kA at 240 V AC covers most industrial service-entrance fault levels; at 480 V it still holds 35 kA under UL 60947. That keeps SCCR coordination simple in a 480Y/277 V panel. Rated for continuous duty, category A (IEC 60947-2), AC-3 switching (IEC 60947-4-1). Phase failure sensitivity built in per IEC 60947-4-1 — no external relay needed for three-phase motor protection. Pollution degree 3, IP40 enclosure, IK07 impact resistance.

Frequently asked questions

What is the color and depth of GV4PEM03N?

Color is Gray RAL 7016; depth is 4.6 in (116 mm).

What compliance standards does GV4PEM03N meet?

Certified to CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-4-1, and EN/IEC 60947-2. Fire resistance tested at 960 °C per IEC 60695-2-11.