The Schneider GV4PEM07N6 is a 7 A, 3-pole motor circuit breaker from the TeSys Deca range, rated for motor protection with a 100 kA breaking capacity at 240 V AC — that SCCR headroom covers most 240 V panels without a downstream fuse. Magnetic tripping current is set at 119 A, so on a short-circuit above that threshold it opens fast, while the thermal-magnetic element handles overload profiles per IEC 60947-4-1. The motor power kW table covers from 1.5 kW up to 7.5 kW depending on voltage (400–690 V AC), which gives flexibility across common European and North American line voltages. Electrical durability is rated at 40,000 cycles at AC-3 440 V, so it's built for moderate-duty motor starts.
Dimensions are 6.1 in high, 3.2 in wide, 4.6 in deep — fits a compact panel footprint. Connection pitch is 27 mm without spreaders, 35 mm with; terminals accept lugs or ring terminals up to 95 mm². Operates in any position, IP40 front, IK07 impact resistance. For panel heat, each pole dissipates 4.6 W at rated current.