The GV4PEM115N6 from Schneider's TeSys Deca line is a 115 A, 3-pole motor circuit breaker with electronic thermal-magnetic trip, built for AC-3 motor duty. The continuous duty rating matches IEC 60947-4-1, meaning it can carry the motor load indefinitely when properly sized.
Dimensions are 6.1 x 3.2 x 4.6 in (155 x 81 x 116 mm), with connection pitch of 1.06 in (27 mm) without spreaders or 1.4 in (35 mm) with. Terminals accept lugs or ring terminals up to 95 mm² on the line side and 10 mm² for control wiring. Tightening torque is 9 N·m for power connections, 5 N·m for control.
Electrical durability is 10,000 cycles at AC-3 440 V at In/2, and 5,000 at full In. Mechanical durability is 40,000 cycles. Maximum operating rate is 25 cycles per hour. Power dissipation is 4.6 W per pole, so thermal management in dense panels is straightforward.