Schneider Electric IL0301P252
MPNIL0301P252
Active
I-Line circuit breaker, 1 Pole L2, 30A rating, 25kA, TMD trip unit adapted ComPacT NSX new generation
$74.93 – $183.10Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Protection type | L : for overload protection (long time) I : for short-circuit protection (magnetic) |
| Range of product | ComPacT NSX100...250 |
| Product or component type | Circuit breaker |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type ii | Fixed |
| Long-time pick-up adjustment type ir (thermal protection) | Fixed |
| Voltage | 800 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Ue] rated operational voltage | 277 V AC 50/60 Hz conforming to EN/IEC 60947-2 250 V DC conforming to EN/IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
| Current | 30 A at 40 °C |
| [Ics] rated service short-circuit breaking capacity | 25 kA at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
All specifications
| Parameter | Value |
|---|---|
| [Icu] rated ultimate short-circuit breaking capacity | 25 kA Icu at 220/240 V AC 50/60 Hz conforming to EN 60947-2 |
| Poles | 1P |
| Utilisation category | Category A |
| IK degree of protection | IK07 conforming to IEC 62262 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Mounting location | I-Line |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 95 % |
| Operating altitude | 0...2000 m without derating 2000 m...5000 m without derating |
| Color | Grey |
| Depth | 86 mm |
| Width | 35 mm |
| Height | 161 mm |
| Electrical durability | 20000 cycles at 277 V In 10000 cycles at 277 V In/2 |
| Mechanical durability | 20000 cycles |
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 |
| Range | I-Line |
| Trip unit name | TM-D |
| Device short name | NSX100B |
| Safety category | N |
| Device application | Distribution |
| Trip unit technology | Thermal-magnetic |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Trip unit protection functions | LI |
| Ambient air temperature for storage | -50...85 °C |
| Ambient air temperature for operation | -25...70 °C |
| [Ir] long-time protection pick-up adjustment range | 1 In |
| [Ii] instantaneous protection pick-up adjustment range | 300 A |
MPN
IL0301P252