Specifications
| Parameter | Value |
|---|---|
| Display type | LCD display |
| Type of network | 1P + N 3P 3P + N |
| Type of setting | Alarm threshold: settable per feeder |
| Electrical circuit type | Power circuit Control/command circuit |
| Input (Type of measurement) | History of alarms Network insulation resistance, range: 200 Ohm...250 kOhm Earth leakage capacitance, range: 0.1...15 µF |
| Product or component type | Insulation fault locator |
| Physical (Type of installation) | Indoor |
| Communications & management (Dry contact type) | 1 C/O standard or fail-safe |
| Input (Network rated voltage) | 0...480 V - AC at 45...440 Hz (device connected to phase) 0...830 V - AC at 45...440 Hz (device connected to neutral) 480...1000 V - AC at 45...440 Hz (device connected to phase with PHT1000 subassembly) 830...1000 V - AC at 45...440 Hz (device connected to neutral with PHT1000 subassembly) 0...480 V - DC 480...1000 V - DC (device connected with PHT1000) |
| Power requirements ([Us] rated supply voltage) | 100...300 V (LN) AC 50/60 Hz tolerance: +/- 15 % 100...440 V AC 50/60 Hz tolerance: +/- 15 % 80...120 V (LN) AC 400 Hz tolerance: +/- 15 % 100...440 V DC tolerance: +/- 15 % |
| Communications & management (Signalling circuit voltage) | 250 V - AC at 6 A 48 V - DC at 1 A |
| Power quality analysis | Transient capture |
All specifications
| Parameter | Value |
|---|---|
| Power requirements (Overcurrent protection) | 1 A |
| Power requirements (Power consumption in w) | 10 W |
| Power requirements (Power consumption in VA) | 26 VA |
| IP degree of protection | Case: IP20 Front face: IP54 |
| Communications & management (Self-test) | Auto test at start and every 5h Remote test Manual |
| Communications & management (Response time) | <= 5 s |
| Communications & management (Fault event log) | Alarm logs |
| Communications & management (Local signalling) | Yellow indicator light: insulation fault Yellow flashing indicator light: communication Green/red indicator light: product status Green indicator light: satisfactory insulation LCD display: transient fault |
| Communications & management (Threshold setting) | Alarm: 200 Ohm...200 kOhm |
| Communications & management (Alarm optional delay) | 0...120 min for signalling circuit |
| Communications & management (Communication port protocol) | Modbus RS485 |
| Physical (Mounting mode) | Flush-mounted (panel) Clip-on (DIN rail) |
| Physical (Mounting position) | Vertical Horizontal |
| Connections - terminals | Power supply: removable screw terminal block0.2...2.5 mm² Output relay: removable screw terminal block0.2...2.5 mm² Toroids inputs: removable screw terminal block0.2...1.5 mm² Communication: removable screw terminal block0.2...2.5 mm² Voltage inputs: removable screw terminal block0.2...2.5 mm² |
| Response time | 1 s 1/5th of set filtering time 8 s 1/5th of set filtering time 80 s 1/5th of set filtering time |
| Relative humidity | 5...92 % |
| Operating altitude | <= 3000 m |
| Conformance (Pollution degree) | 2 |
| Physical (Depth) | 59 mm |
| Physical (Width) | 108 mm |
| Physical (Height) | 110 mm |
| Physical (Material) | Thermoplastic |
| Physical (Cut-out dimensions) | 92 x 104 mm |
| Conformance (Standards) | IEC 60364-4-41 IEC 61010-1 IEC 60364-5-51 IEC 61557-9 IEC 61557-15 IEC 61326-2-4 UL 61010-1 |
| Range | Vigilohm |
| Accuracy | +/- 15 % |
| Application | Marine application Environment - standard application |
| Network size | Large |
| User language | Spanish German Italian Russian French Chinese English Portuguese |
| Earthing system | IT HRG |
| Device short name | IFL12MC |
| Network capacitance | Highly polluted |
| Overvoltage category | III 300 V II 600 V |
| Information displayed | Resistance value Capacitance value Evolution of resistance in graph |
| Input (Number of channels) | 12 |
| Input (Monitoring function) | Detection of toroids connection automatic Detection of toroids connection manual mode Detection of IM400 injection current permanent |
| Mechanical characteristic | Long-term storage class 1M11 conforming to IEC 60721-3-1 Transport class 2M4 conforming to IEC 60721-3-2 Stationary use class 3M11 conforming to IEC 60721-3-3 |
| Configurable filtering time | 5 s 40 s 400 s |
| Environmental characteristic | Exposure to damp heat not in service conforming to IEC 60068-2-30 Exposure to damp heat in service conforming to IEC 60068-2-56 Salt mist conforming to IEC 60068-2-52 Long-term storage class 1K22 conforming to IEC 60721-3-1 Transport class 2K11 conforming to IEC 60721-3-2 Stationary use at weatherprotected locations class 3K24 conforming to IEC 60721-3-3 |
| Ambient air temperature for storage | -40...85 °C |
| Ambient air temperature for operation | -25...70 °C |
MPN