Skip to main content
Schneider Electric JDA36175

Schneider JDA36175 Molded Case Breaker 175A

MPNJDA36175
Active

Breaker, Molded Case, 175A, 600VAC, 14-25kAIC, 3P, Power Pact J|Breaker, Molded Case, 175 Amp, 600 Volt AC, 14 - 25 kAIC, 3-Pole, Power Pact J, Plug In

$1,359.01 – $1,827.28Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

JDA36175 key specifications
ParameterValue
Control typeToggle
Protection typeOverload protection Short-circuit protection
Product or component typeCircuit breaker
Voltage750 V IEC 60947-2
[Ue] rated operational voltage600 V AC 50/60 Hz IEC 60947-3
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity25 kA 240 V AC 50/60 Hz UL 489 18 kA 480 V AC 50/60 Hz 14 kA 600 V AC 50/60 Hz 20 kA 250 V DC
Line rated current175 A
Magnetic hold current875 A
Breaking capacity codeD
Continuous current rating80 %
Magnetic tripping current1750 A

All specifications

JDA36175 additional specifications
ParameterValue
[Ics] rated service breaking capacity25 kA 220/240 V AC 50/60 Hz IEC 60947-2 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 20 kA 250 V DC IEC 60947-2 20 kA 500 V DC IEC 60947-2
Power wire stripping length1.0 in (25 mm)
Network frequency50/60 Hz
Poles3P
Phase connectionABC
Utilisation categoryCategory A
IP degree of protectionFront cover IP40
Communication interfaceModbus
Mounting modeI-Line bracket)
Mounting height4.5 in (114.3 mm)
Mounting supportBracket
Terminal identifierAL175JD
Electrical connectionI-Line connection, line Lugs, load
Pollution degree3
Operating altitude< 6561.68 ft (2000 m) without derating 5000 m with derating
Depth3.4 in (86 mm)
Width4.09 in (104 mm)
Height7.5 in (191 mm)
StandardsUL CSA NEMA NOM-003-SCFI-2000 IEC 60947-2
CategoryUS10DE201112
AWG gaugeAWG 4...AWG 4/0 aluminium/copper terminal
Quality labelsCE
Number of slots2 auxiliary switch OF plug-in) 1 alarm switch SD plug-in) 1 overcurrent trip switch SDE plug-in) 1 voltage release MN or MX plug-in)
Local signallingSwitched off (OFF) 1 trip indicator green)
Tightening torque221.3 lbf.in (25 N.m) 0.04...0.1 in² (25...95 mm²) (AWG 4...AWG 4/0)
Trip unit technologyThermal-magnetic
Suitability for isolationYes IEC 60947-2
Circuit breaker applicationHACR rated
Long time pick-up adjustment range0.25...1 x In
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
MPN
JDA36175