Skip to main content
Schneider Electric JDF36000F25

Schneider Electric JDF36000F25

MPNJDF36000F25
Active

MOLDED CASE CB FRAME 600V 250A|Square D,MOLDED CASE CB FRAME 600V 250A,150...250 A,150...250 A,25 kA 240 V AC-18 kA 480 V AC-14 kA 600 V AC,250 V DC-600 V AC,250 V DC-600 V AC,3P,D,UL Listed,circuit breaker,fixed

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

JDF36000F25 key specifications
ParameterValue
Control typeToggle
Protection typeOverload protection Short-circuit protection
Product or component typeCircuit breaker
Voltage750 V IEC 60947-2
[Ue] rated operational voltage600 V AC 50/60 Hz IEC 60947-3
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity25 kA 240 V AC 50/60 Hz UL 489 18 kA 480 V AC 50/60 Hz 14 kA 600 V AC 50/60 Hz 20 kA 250 V DC
Line rated current150...250 A
Magnetic hold current875 A
Breaking capacity codeD
Continuous current rating80 %
Magnetic tripping current1750 A

All specifications

JDF36000F25 additional specifications
ParameterValue
[Ics] rated service breaking capacity25 kA 220/240 V AC 50/60 Hz IEC 60947-2 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 20 kA 250 V DC IEC 60947-2 20 kA 500 V DC IEC 60947-2
Power wire stripping length1.0 in (25 mm)
Network frequency50/60 Hz
Poles3P
Phase connectionCA
Utilisation categoryCategory A
IP degree of protectionFront cover IP40
Communication interfaceModbus Ethernet
Mounting modeUnit mount busbar)
Mounting height4.5 in (114.3 mm)
Mounting supportBusbar
Terminal identifierAL175JD
Electrical connectionBusbar connection, line Busbar connection, load
Pollution degree3 IEC 60947-1
Operating altitude< 6561.68 ft (2000 m) without derating 5000 m with derating
Depth3.4 in (86 mm)
Width4.09 in (104 mm)
Height7.5 in (191 mm)
StandardsUL CSA NEMA NOM-003-SCFI-2000 IEC 60947-2
RangePowerPact
AWG gaugeAWG 4...AWG 4/0 aluminium/copper terminal
Quality labelsCE
Number of slots2 auxiliary switch OF plug-in) 1 alarm switch SD plug-in) 1 overcurrent trip switch SDE plug-in) 1 voltage release MN or MX plug-in)
Installed deviceTrip unit field installable
Tightening torque221.3 lbf.in (25 N.m) 0.04...0.1 in² (25...95 mm²) (AWG 4...AWG 4/0)
Device applicationDistribution
Suitability for isolationYes IEC 60947-2
Circuit breaker applicationHACR rated
Long time pick-up adjustment range0.25...1 x In
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
MPN
JDF36000F25