Skip to main content
Schneider Electric JGP36250

Schneider Electric JGP36250

MPNJGP36250
Active

MOLDED CASE CIRCUIT BREAKER 600V 250A|MOLDED CASE CIRCUIT BREAKER 600V 250A

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

JGP36250 key specifications
ParameterValue
Control typeToggle
Protection typeOverload protection Short-circuit protection
Product or component typeCircuit breaker
Voltage750 V IEC 60947-2
[Ue] rated operational voltage600 V AC 50/60 Hz IEC 60947-3
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacity65 kA 240 V AC 50/60 Hz UL 489 35 kA 480 V AC 50/60 Hz UL 489 18 kA 600 V AC 50/60 Hz UL 489 20 kA 250 V DC UL 489 20 kA 500 V DC UL 489
Line rated current250 A
Magnetic hold current1250 A
Breaking capacity codeG
Continuous current rating80 %
Magnetic tripping current2500 A

All specifications

JGP36250 additional specifications
ParameterValue
[Ics] rated service breaking capacity65 kA 220/240 V AC 50/60 Hz IEC 60947-2 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 20 kA 250 V DC IEC 60947-2 20 kA 500 V DC IEC 60947-2
Power wire stripping length1.0 in (25 mm)
Network frequency50/60 Hz
Poles3P
Phase connectionBA
Utilisation categoryCategory A
IP degree of protectionFront cover IP40
Communication interfaceModbus Ethernet
Mounting modeUnit mount lug)
Mounting height4.5 in (114.3 mm)
Mounting supportLug
Terminal identifierAL250JD
Electrical connectionTerminal nut, line Lugs, load
Pollution degree3 IEC 60947-1
Operating altitude< 6561.68 ft (2000 m) without derating 5000 m with derating
Depth3.4 in (86 mm)
Width4.09 in (104 mm)
Height7.5 in (191 mm)
StandardsUL CSA NEMA NOM-003-SCFI-2000 IEC 60947-2
RangePowerPact
CategoryUS10DE201115
AWG gaugeAWG 3/0...350 kcmil aluminium/copper terminals
Quality labelsCE
Number of slots2 auxiliary switch OF plug-in) 1 alarm switch SD plug-in) 1 overcurrent trip switch SDE plug-in) 1 voltage release MN or MX plug-in)
Local signallingSwitched off (OFF) 1 trip indicator green)
Tightening torque221.3 lbf.in (25 N.m) 0.1...0.3 in² (95...185 mm²) (AWG 3/0...350 kcmil)
Device applicationDistribution
Trip unit technologyThermal-magnetic
Suitability for isolationYes IEC 60947-2
Circuit breaker applicationHACR rated
Long time pick-up adjustment range0.25...1 x In
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
MPN