Specifications

K2B004T key specifications
ParameterValue
Range of productHarmony K
Product or component typeCam switch body
Voltage690 V 3)IEC 60947-1
[Uimp] rated impulse withstand voltage4 kV in isolating function 6 kV IEC 947-1
Short-circuit current10000 A
Short-circuit protection20 A cartridge fuse gG
[Ie] rated operational current AC2 A 500 V AC-15 IEC 947-5-1 3 A 400 V AC-15 IEC 947-5-1 4 A 230 V AC-15 IEC 947-5-1 8 A 400 V AC-3 3 phase IEC 947-3 10.8 A 400 V AC-23A 3 phase IEC 947-3 14.6 A 230 V AC-23A 3 phase IEC 947-3 4.7 A 690 V AC-3 3 phase IEC 947-3 6.4 A 690 V AC-23A 3 phase IEC 947-3 6.5 A 500 V AC-3 3 phase IEC 947-3 8.3 A 230 V AC-3 3 phase IEC 947-3 8.9 A 500 V AC-23A 3 phase IEC 947-3
[Ith] conventional free air thermal current20 A
[Ithe] conventional enclosed thermal current16 A
Rated operational power in1300 W AC-3, 230 V 1 phase IEC 947-3 14000 W AC-21, 400 V 3 phase IEC 947-3 17000 W AC-21, 500 - 660 V 3 phase IEC 947-3 2200 W AC-3, 230 V 3 phase IEC 947-3 2200 W AC-3, 400 V 1 phase IEC 947-3 4000 W AC-23A, 230 V 3 phase IEC 947-3 4000 W AC-3, 400 V 3 phase IEC 947-3 4000 W AC-3, 500 V 3 phase IEC 947-3 4000 W AC-3, 690 V 3 phase IEC 947-3 5500 W AC-23A, 400 V 3 phase IEC 947-3 5500 W AC-23A, 500 V 3 phase IEC 947-3 5500 W AC-23A, 690 V 3 phase IEC 947-3 8000 W AC-21, 230 V 3 phase IEC 947-3
Poles description1P
Product mountingFront mounting

All specifications

K2B004T additional specifications
ParameterValue
Electrical connectionCaptive screw clamp terminals flexible 2 x 1.5 mm² Captive screw clamp terminals solid 1 x 2.5 mm²
Shock resistance30 gn IEC 68-2-27
Vibration resistance5 gn 10...150 Hz)IEC 68-2-6
Electrical shock protection classClass II conforming to IEC 536 Class II conforming to NF C 20-030
Bezel materialPlastic
Electrical durability200000 cycles AC-23 200000 cycles AC-3 600000 cycles AC-15 600000 cycles AC-21
Mechanical durability1000000 cycles
StandardsCENELEC EN 50013 EN/IEC 60947-3 power circuit EN/IEC 60947-5-1 control circuit
ReturnSpring return from 30° to 0° Spring return from 330° to 0°
Category18406-WORLD SERVICE PARTS(OTHER OP INT)
Fixing modeØ 22 mm hole
Off positionWith Off position
Component nameK2
Switching angle30 °
Positive openingWith
Contact operationSlow-break
Cam switch functionOFF-ON switch
PositionsRight: 0° - 30° Left: 0° - 330°
Protective treatmentTC
Maximum operating rate2.5 cyc/mn AC-21 2.5 cyc/mn AC-23 2.5 cyc/mn AC-3 8.333 cyc/mn AC-15
Sub-assembly compositionContact blocks + fixing plate
Ambient air temperature for storage-40...158 °F (-40...70 °C)
Ambient air temperature for operation-13...131 °F (-25...55 °C)