Skip to main content
Schneider Electric LA4EM250FF — Contactors

Schneider LA4EM250FF TeSys F Electronic Control Module, 100-

MPNLA4EM250FF
Obsolete

Schneider Electric TeSys F electronic control module, LA4EM250FF, for LXEFF250 coil, 115 A/150 A AC-3, 100...250 V AC 50/60 Hz / 100...380 V DC control circuit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LA4EM250FF — Identification
ParameterValue
Product / component typeElectronic control module
Series / rangeTeSys

Product details

The Schneider LA4EM250FF is an electronic control module in the TeSys F range, designed specifically to drive the LXEFF250 coil on TeSys F contactors rated 115 A / 150 A AC-3. It accepts a wide control voltage — 100...250 V AC 50/60 Hz or 100...380 V DC — and includes built-in bidirectional peak limiting on the coil drive, which suppresses voltage spikes without needing an external varistor or RC snubber. The module's input is compatible with PLC 24 V DC outputs conforming to IEC 61131-2 Type 2, with an off-state threshold of 0...5 V and on-state from 11...30 V. This means a standard 24 V PLC output card can switch the contactor directly through this module, simplifying the control wiring.

Sourcing reality — obsolete part

This part is marked obsolete by the manufacturer. There is no official direct replacement order code listed in the lifecycle record. The module's heat dissipation of 2.2...5.5 W and inrush of 270...320 W (at 20 °C) are still relevant for panel thermal calculations if you're fitting an NOS unit into an existing design. The control voltage limits are wide: operational range is 85...275 V AC (50/60 Hz) and 85...418 V DC at 55 °C, with dropout at 60 V AC or 45 V DC. That gives decent ride-through on a sagging DC bus, but the hold-in consumption is modest — 2.5...4 W DC or 4.5...7 VA AC.

Integration notes

Tighten to 0.6 N·m. The module is rated for 10 million mechanical cycles and can operate at up to 2400 cycles per hour at 55 °C — figures that matter if this is going into a high-speed pick-and-place or packaging line.

Frequently asked questions

What contactor does this module work with?

The LA4EM250FF is designed for use with the LXEFF250 coil, which fits TeSys F contactors rated 115 A / 150 A AC-3. The module is a required companion device for that coil.

What control voltage does it accept?

The module accepts 100...250 V AC 50/60 Hz or 100...380 V DC as the nominal control voltage. The operational range extends to 85...275 V AC and 85...418 V DC at 55 °C.

Can a 24 V PLC output drive this module directly?

Yes, the input is compatible with PLC 24 V DC outputs per IEC 61131-2 Type 2. The on-state threshold is 11...30 V, so a standard 24 V PLC output card can switch the contactor through this module.

MPN
LA4EM250FF