Skip to main content
Schneider Electric LAD9AP3D1 — Motor Control Accessories

Schneider Electric LAD9AP3D1 Control Connection Module

MPNLAD9AP3D1
Obsolete

Schneider Electric TeSys D LAD9AP3D1 control connection module, for direct motor starter GV2ME-GV3P, 18 A per starter / 60 A power circuit, fixed mounting, IP40.

$276.03Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LAD9AP3D1 — Identification
ParameterValue
Product / component typeControl connection module
Product rangeTeSys D

Electrical

LAD9AP3D1 — Electrical
ParameterValue
Rated operational voltage (Ue)690 V
Rated current (In)18 A per starter 60 A for power circuit conforming to IEC 60439-1 60 A per sub-base conforming to IEC 60439-1
Network frequency50/60 Hz

Cable & Connector

LAD9AP3D1 — Cable & Connector
ParameterValue
Terminal connection capacityControl circuit: spring terminal 2 cable(s) 1.5 mm² flexible with cable end Control circuit: spring terminal 2 cable(s) 2.5 mm² flexible Control circuit: spring terminal 2 cable(s) 2.5 mm² solid Power circuit: spring terminal 3 cable(s) 16 mm² flexible with cable end Power circuit: spring terminal 3 cable(s) 25 mm² flexible Power circuit: spring terminal 3 cable(s) 25 mm² solid

Mechanical

LAD9AP3D1 — Mechanical
ParameterValue
Mounting modeFixed

Environmental

LAD9AP3D1 — Environmental
ParameterValue
IP protection ratingIP40
Operating ambient temperature-5...40 °C wall mounted -5...60 °C floor mounting
Storage ambient temperature-40...70 °C

Approvals

LAD9AP3D1 — Approvals
ParameterValue
Conformance standardsIEC 60439-1

Product details

What This Module Does

The LAD9AP3D1 is a control connection module from the TeSys D range, designed to wire the control circuit of a direct motor starter using a GV2ME or GV3P circuit breaker. It carries 18 A per starter and handles 60 A for the power circuit per IEC 60439-1, with a rated insulation voltage of 750 V and operational voltage of 690 V.

Mounting and Wiring

Mounts fixed on a plate or on 2 x 35 mm symmetrical DIN rail — the same footprint as the TeSys D contactor range, so it fits into existing panel layouts without re-drilling. Spring terminals on both control and power circuits: control side accepts 2 x 1.5 mm² flexible with ferrule, or 2 x 2.5 mm² solid; power side takes up to 3 x 25 mm² solid or flexible.

Sourcing Reality — Obsolete Part

We source it through independent surplus channels; quantities are lot-specific and confirmed at RFQ.

Frequently asked questions

How do I get current pricing and availability for LAD9AP3D1?

Submit an RFQ through this listing.

What standards does the LAD9AP3D1 comply with?

It is designed to IEC 60439-1 for low-voltage switchgear and controlgear assemblies, with pollution degree 3 and a rated short-time withstand current of 9.1 kA for 70 ms.

MPN