How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Range of product | TeSys D |
| Product or component type | Control connection module |
| Climatic withstand | Resistance to incandescent wire: 960 °C conforming to IEC 60695-2-1 |
| Voltage | 750 V |
| [Ue] rated operational voltage | 690 V |
| [Uimp] rated impulse withstand voltage | 6 kV for power circuit |
| [Icw] rated short-time withstand current | 9.1 kA for 70 ms conforming to IEC 60439-1 |
| Current | 18 A per starter 60 A for power circuit conforming to IEC 60439-1 60 A per sub-base conforming to IEC 60439-1 |
| [Ics] rated service breaking capacity | 50 kA at 415 V conforming to IEC 60439-1 |
| Supply maximum power | 0.36 W |
| Network frequency | 50/60 Hz |
| IP degree of protection | IP40 |
All specifications
| Parameter | Value |
|---|---|
| Mounting mode | Fixed |
| Mounting support | Mounting plate 2 x 35 mm symmetrical DIN rail |
| Connections - terminals | Control circuit: spring terminal 2 cable(s) 1.5 mm² flexible with cable end Control circuit: spring terminal 2 cable(s) 2.5 mm² flexible Control circuit: spring terminal 2 cable(s) 2.5 mm² solid Power circuit: spring terminal 3 cable(s) 16 mm² flexible with cable end Power circuit: spring terminal 3 cable(s) 25 mm² flexible Power circuit: spring terminal 3 cable(s) 25 mm² solid |
| Pollution degree | 3 |
| Product weight | 0.19 kg |
| Standards | IEC 60439-1 |
| Derating factor | 20 % of Imax GV2 circuit breaker 60 °C |
| Device short name | LAD9 |
| Mechanical robustness | Shocks 11 ms half sine wave acceleration (15 gn) conforming to IEC 60068-2-27 Vibrations 3...100 Hz (0.7 gn) conforming to BV Vibrations 3...100 Hz (0.7 gn) conforming to IEC 60068-2-6 Vibrations 3...100 Hz (0.7 gn) conforming to LR Vibrations 2...100 Hz (4 gn) conforming to BV Vibrations 2...100 Hz (4 gn) conforming to IEC 60068-2-6 Vibrations 2...100 Hz (4 gn) conforming to LR |
| Minimum clearance distance | 30 mm |
| Electromagnetic compatibility | Electrostatic discharge immunity test: , 3, conforming to IEC 61000-4-2 Fast transients immunity test: , 3, conforming to IEC 61000-4-4 Immunity to radiated fields: (26...1000 MHz), 10 V/m, conforming to IEC 61000-4-3 Radiated radio-frequency electromagnetic field immunity test: (0.15...80 MHz), 10 V, conforming to IEC 61000-4-6 Surge immunity test: (8...20 µs in differential mode), 0.6 kV, conforming to IEC 61000-4-5 Surge immunity test: (1.2...50 µs in common mode), 2 kV, conforming to IEC 61000-4-5 |
| Ambient air temperature for storage | -40...70 °C |
| Ambient air temperature for operation | -5...40 °C wall mounted -5...60 °C floor mounting |