Skip to main content
Schneider Electric LC1BM33U22

Schneider Electric LC1BM33U22

MPNLC1BM33U22
Obsolete

bar-mounted contactor - TeSys LC1-BM - 3 poles - AC-3 440V 1000 A - coil 240V AC

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1BM33U22 key specifications
ParameterValue
Coil typeStandard
Control circuit typeAC
Product or component typeContactor
Coil voltage240 V AC 50...400 Hz
Voltage1000 V - power circuit IEC 60158-1 1000 V - power circuit IEC 60947-4 1500 V - power circuit VDE 0110 group C
Control circuit voltage limitsDrop-out: 0.3...0.5 Uc at 50...400 Hz Operational: 0.85...1.1 Uc at 50...400 Hz
[Ue] rated operational voltagePower circuit <= 1000 V AC 50/60 Hz
Breaking capacity10000 A at 440 V for power circuit conforming to IEC 60158-1 10000 A at 440 V for power circuit conforming to IEC 60947-4 4000 A at 1000 V for power circuit conforming to IEC 60158-1 4000 A at 1000 V for power circuit conforming to IEC 60947-4 8000 A at 660...690 V for power circuit conforming to IEC 60158-1 8000 A at 660...690 V for power circuit conforming to IEC 60947-4 9000 A at 500 V for power circuit conforming to IEC 60158-1 9000 A at 500 V for power circuit conforming to IEC 60947-4
[Ie] rated operational current1250 A (at 1000 A (at <131 °F (55 °C)) AC AC-3 for power circuit
[Ith] conventional free air thermal current1250 A (at 104 °F (40 °C)) for power circuit
Motor power530 kW at 1000 V AC 50/60 Hz 280 kW at 220...230 V AC 50/60 Hz 500 kW at 380...400 V AC 50/60 Hz 530 kW at 415 V AC 50/60 Hz 560 kW at 440 V AC 50/60 Hz 600 kW at 500 V AC 50/60 Hz 670 kW at 660...690 V AC 50/60 Hz 160 kW at 400 V AC
Inrush power in1300 VA

All specifications

LC1BM33U22 additional specifications
ParameterValue
Power dissipation per pole180 W AC-3 - Ith 1250 A 280 W AC-1 - Ith 1250 A
Hold-in power consumption in31 VA 50/60 Hz
Poles description3P
Pole contact composition3 NO
Utilisation categoryAC-3 AC-1
Mounting modeFixed
Mounting supportNotched mounting rails Bar support bracket
Operating altitude9842.52 ft (3000 m) without derating
Depth18.7 in (475 mm)
Width22.4 in (570 mm)
Height19.3 in (490 mm)
Mechanical durability1200000 cycles
StandardsIEC 60158-1 IEC 60947-4 BS 5424 VDE 0660 NF C 63-110
RangeTeSys
Category18402-WORLD SERVICE PARTS(CONTROL ACCESS)
Operating time100...150 ms closing 50...100 ms opening
Average impedance0.18 mOhm - Ith 1250 A 50 Hz for power circuit
Device short nameLC1BM
Tightening torquePower circuit 309.8 lbf.in (35 N.m) bars
Protective treatmentTC TH
Contactor applicationMotor-heating-lighting
Associated fuse rating1200 A aM at 1200 A gI at 1500 A gI at <= 440 V for power circuit
Maximum operating rate120 cyc/h 131 °F (55 °C)
Irms rated making capacity10000 A at 1000 V AC for power circuit conforming to IEC 60158-1 10000 A at 1000 V AC for power circuit conforming to IEC 60947-4
Auxiliary contact composition2 NO + 2 NC
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)
MPN
LC1BM33U22