Skip to main content
Schneider Electric LC1BM34M22

Schneider Electric LC1BM34M22

MPNLC1BM34M22
Obsolete

TeSys B bar-mounted contactor - 4 poles - AC-1 440V 1250 A - coil 220V AC

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1BM34M22 key specifications
ParameterValue
Coil typeStandard
Control circuit typeAC
Product or component typeContactor
Coil voltage220 V AC 60 Hz
Voltage1000 V - power circuit IEC 60158-1 1000 V - power circuit IEC 60947-4 1500 V - power circuit VDE 0110 group C
Control circuit voltage limitsDrop-out: 0.3...0.5 Uc at 50...400 Hz Operational: 0.85...1.1 Uc at 50...400 Hz
[Ue] rated operational voltagePower circuit <= 1000 V AC 50/60 Hz
Breaking capacity10000 A at 440 V for power circuit conforming to IEC 60158-1 10000 A at 440 V for power circuit conforming to IEC 60947-4 4000 A at 1000 V for power circuit conforming to IEC 60158-1 4000 A at 1000 V for power circuit conforming to IEC 60947-4 8000 A at 660...690 V for power circuit conforming to IEC 60158-1 8000 A at 660...690 V for power circuit conforming to IEC 60947-4 9000 A at 500 V for power circuit conforming to IEC 60158-1 9000 A at 500 V for power circuit conforming to IEC 60947-4
[Ie] rated operational current1250 A (at <104 °F (40 °C)) AC AC-1 for power circuit
[Ith] conventional free air thermal current1250 A (at 104 °F (40 °C)) for power circuit
Inrush power in1600 VA
Power dissipation per pole280 W AC-1 - Ith 1250 A

All specifications

LC1BM34M22 additional specifications
ParameterValue
Hold-in power consumption in47 VA 50/60 Hz
Poles description4P
Pole contact composition4 NO
Utilisation categoryAC-1
Mounting modeFixed
Mounting supportBar support bracket Notched mounting rails
Connections - terminalsbolted connection
Operating altitude9842.52 ft (3000 m) without derating
Depth18.7 in (475 mm)
Width31.1 in (790 mm)
Height19.3 in (490 mm)
Mechanical durability1200000 cycles
StandardsBS 5424 VDE 0660 IEC 60947-4 NF C 63-110 IEC 60158-1
RangeTeSys
Category18402-WORLD SERVICE PARTS(CONTROL ACCESS)
Operating time100...150 ms closing 50...100 ms opening
Average impedance0.18 mOhm - Ith 1250 A 50 Hz for power circuit
Device short nameLC1BM
Tightening torquePower circuit 309.8 lbf.in (35 N.m) bars
Protective treatmentTC TH
Contactor applicationMotor-heating-lighting
Associated fuse rating1200 A aM at 1200 A gI at 1500 A gI at <= 440 V for power circuit
Maximum operating rate120 cyc/h 131 °F (55 °C)
Irms rated making capacity10000 A at 1000 V AC for power circuit conforming to IEC 60158-1 10000 A at 1000 V AC for power circuit conforming to IEC 60947-4
Auxiliary contact composition2 NO + 2 NC
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)
MPN