Schneider Electric LC1BP33FD22
MPNLC1BP33FD22
Obsolete
bar-mounted contactor - TeSys LC1-BP - 3 poles - AC-3 440V 1500 A - coil 110V DC
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Coil type | Standard |
| Control circuit type | DC |
| Product or component type | Contactor |
| Coil voltage | 110 V DC |
| Voltage | 1000 V - for power circuit conforming to IEC 60158-1 1000 V - for power circuit conforming to IEC 60947-4 1500 V - for power circuit conforming to VDE 0110 group C |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc Drop-out: 0.35...0.5 Uc |
| [Ue] rated operational voltage | Power circuit: <= 1000 V AC 50/60 Hz |
| Breaking capacity | 12000 A at 500 V for power circuit conforming to IEC 60158-1 12000 A at 500 V for power circuit conforming to IEC 60947-4 15000 A at 440 V for power circuit conforming to IEC 60158-1 15000 A at 440 V for power circuit conforming to IEC 60947-4 5000 A at 1000 V for power circuit conforming to IEC 60158-1 5000 A at 1000 V for power circuit conforming to IEC 60947-4 9000 A at 660...690 V for power circuit conforming to IEC 60158-1 9000 A at 660...690 V for power circuit conforming to IEC 60947-4 |
| [Ie] rated operational current | 2000 A (at 1500 A (at <55 °C) AC AC-3 for power circuit |
| [Ith] conventional free air thermal current | 2000 A (at 40 °C) for power circuit |
| Motor power | 425 kW at 220...230 V AC 50/60 Hz 670 kW at 1000 V AC 50/60 Hz 700 kW at 500 V AC 50/60 Hz 750 kW at 380...400 V AC 50/60 Hz 750 kW at 660...690 V AC 50/60 Hz 800 kW at 415 V AC 50/60 Hz 800 kW at 440 V AC 50/60 Hz |
| Inrush power in | 1100 W |
All specifications
| Parameter | Value |
|---|---|
| Power dissipation per pole | 290 W AC-3 - Ith 2000 A 520 W AC-1 - Ith 2000 A |
| Hold-in power consumption in | 31 W |
| Poles description | 3P |
| Pole contact composition | 3 NO |
| Utilisation category | AC-1 AC-3 |
| Mounting mode | Fixed |
| Mounting support | Bar support bracket Notched mounting rails |
| Connections - terminals | Power circuit: bars 3 x - busbar cross section: 100 x 5 mm |
| Operating altitude | 3000 m without derating |
| Depth | 475 mm |
| Width | 790 mm |
| Height | 490 mm |
| Mechanical durability | 1200000 cycles |
| Standards | BS 5424 NF C 63-110 VDE 0660 IEC 60158-1 IEC 60947-4 |
| Range | TeSys |
| Operating time | 100...150 ms closing 20...40 ms opening |
| Average impedance | 0.13 mOhm - Ith 2000 A 50 Hz for power circuit |
| Device short name | LC1BP |
| Tightening torque | Power circuit: 35 N.m - on bars |
| Protective treatment | TC TH |
| Contactor application | Motor-heating-lighting |
| Associated fuse rating | 1600 A aM at 2000 A gI at <= 440 V for power circuit |
| Maximum operating rate | 120 cyc/h 55 °C |
| Irms rated making capacity | 15000 A at 1000 V AC for power circuit conforming to IEC 60158-1 15000 A at 1000 V AC for power circuit conforming to IEC 60947-4 |
| Auxiliary contact composition | 2 NO + 2 NC |
| Ambient air temperature for storage | -60...80 °C |
| Ambient air temperature for operation | -5...55 °C |
MPN
LC1BP33FD22